    Goodman heat pump does not click off when thermostat reaches desired temp
    I have a goodman heat pump model #a32-10 controlled by a Honeywell Thermostat model #RTH3100C-installed last winter.
    Temperature in South Carolina this week has been ranging in the day in the lower to mid-40's and at night ranging in 20's or teens. I usually keep thermostat set between 66-68. The problem I am having is that once set temp is reached the heat pump continues to run. If I lower the set temp the unit will turn itself off. However, once the new lower set temp is reached the problem with it continuing to run recurs.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Jan 7, 2010, 03:47 AM
    A heat pump only does what the thermostat tells it to do unless it is in the defrost mode or has a stuck contactor or relay. If the thermostat is set correctly this should not happen unless the thermostat is having a problem or is somehow wired wrong.

    Hw ere is your install guide. Pay close attention to the setup instructions for this thermostat since you have to do the programing to pick the correct system you have etc.

    http://customer.honeywell.com/techli.../69-1889EF.pdf

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman heat pump does not switch on for heat and the AC blows A/H fuses. [ 4 Answers ]

My Goodman heat pump, model GSH130361AD, heat does not switch on (outer unit). When it first went out, the Honeywell T8411R t-stat digital display went blank. First, I tried replacing the stat with other, but they only accommodated 5 wires. Wiring to the Honeywell was 7 wires. I'll come back to...

Heat strip not working on my goodman heat pump [ 1 Answers ]

Heat strip not working on my goodman heat pump

Furnace cycles but never reaches set temp [ 1 Answers ]

I have a gas furnace and a daypart thermostat. The heat level never rises above or below 64 degrees, even though the temperature is set for 72 during the day. This started about 1 week ago. I have replaced batteries in the thermostat, replaced filters - and even replaced the whole thermostat. ...

Heat pump reaches setpoint but won't turn off [ 16 Answers ]

Hi... I have a Janitrol heat pump (I don't know the model number) controlled by a Robertshaw thermostat (model #9520). I am having a problem with the heat pump warming the house to the normal setpoint for comfort (say, 70 or 71) during the day but the heat pump continuing to run. By...

Furnace continues to heat past the desired temp. Setting [ 1 Answers ]

I have a gas furnace with an AC unit. My wife wanted to replace the old mercury thermostat with a new digital model. We bought a Honeywell RTH230B. Now the furnace continues to heat, well past the set temperature on the thermostat. I have to switch the thermostat to the off position to get the...


View more questions Search