    ekg125's Avatar
    ekg125 Posts: 5, Reputation: 1
    New Member
     
    #1

    Sep 28, 2008, 06:43 AM
    Goodman GMP075-3 ignition issue
    I have a Goodman GMP075-3 furnace. The draft inducer comes on, the control board clicks, the ignitor bar glows, the control board clicks again and the glow bar stops glowing. It seems like the gas valve isn't opening to allow gas to ignite, at all. I've replaced a rollout switch, the flame sensor and the control board. What's next? The pressure switch seems to be fine as I can blow and suck in it to make it open and close. I can do the same with the inducer by blowing into the hose and air goes through it without a problem. Could the limit switch need replacing? How about the pressure switch? I haven't put a volt meter on the pressure switch to see if it's passing 24 volts yet. Is it possible that the gas valve itself has gone kaput? I know that Goodman furnaces aren't the best in the world, but I can't afford to replace it just yet. I'd like to be able to make it through this winter first, then I can purchase a new furnace in March.
    ekg125's Avatar
    ekg125 Posts: 5, Reputation: 1
    New Member
     
    #2

    Sep 28, 2008, 10:18 AM

    I just checked and the pressure switch and limiter are both reading 28 volts. What now?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #3

    Sep 28, 2008, 03:00 PM
    If you have a flame sensor clean it.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #4

    Sep 28, 2008, 05:36 PM

    Do you have one or two pressure switches? If you are putting your tester leads to the two terminals on the pressure switch, you should not be reading 28 when the pressure switch is closed.
    Turn the power of to the furnace, then turn it back on and wait for about three seconds, then phisically suck on the hose to the pressure switch, make sure you suck hard enough to keep the switch closed. See if the furnace lights.
    Please let me know if this works, if not , we will go to step two.
    I have worked on goodmans, they are actually a very good funace(at least the newer ones) very easy to trouble shoot and fix.
    ekg125's Avatar
    ekg125 Posts: 5, Reputation: 1
    New Member
     
    #5

    Sep 29, 2008, 05:03 AM
    HVAC1000, I tried cleaning the flame sensor once, with some fine steel wool, but it didn't work, so as I stated, I have replaced it altogether, along with 1 rollout switch and a new control board.

    Mygirlsdad77, I have only 1 pressure switch, and will be trying your advice as soon as I drop the kids off at school.

    I should also add that, after the control board clicks the first time, and the ignitor bar begins to glow, there is a second click. After the second click, I get a 27 volt reading on the gas valve, but the ignitor bar turns off, then it fails. After 3 tries, the board displays 1 flashing light (ignition failure).
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Sep 29, 2008, 05:13 AM
    With voltage at the gas valve it should open.
    ekg125's Avatar
    ekg125 Posts: 5, Reputation: 1
    New Member
     
    #7

    Sep 29, 2008, 07:33 AM
    mygirlsdad77, I pulled the hose from the inducer and sucked through it, heard the pressure switch close, but the ignitor bar never glowed. I also tried putting my finger over the hole on the inducer and sucked through the hose, but still never got the bar to glow. The only time it would glow is when I put the hose back on the inducer. It never achieved ignition.

    HVAC1000, It never showed any voltage to the gas valve until the control board clicked the first time, then I heard, and could feel the valve click, too, as I had my finger resting on it as I was checking voltage. Then is when it showed 27 volts. Something seems to be telling it to NOT send any gas to the ignitor.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #8

    Sep 29, 2008, 09:22 AM
    With voltage at the gas valve it should open and lite if the gas valve on the valve itself and all other gas valves are turned on.!
    ekg125's Avatar
    ekg125 Posts: 5, Reputation: 1
    New Member
     
    #9

    Sep 29, 2008, 01:01 PM
    Thanks to both of you guys. My next door neighbor is an electrician and came to help me out. It turns out that the gas valve had gone bad somewhere down the line, and wasn't opening when it was told to. We went to a local HVAC supply house and bought a replacement gas valve for $50, installed it an viola! I now have HEAT! Glorious HEAT!

    Thanks again for all your help!
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #10

    Sep 29, 2008, 01:06 PM
    Good deal and remember if you have power to the valve it should work.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #11

    Sep 29, 2008, 03:47 PM

    Glad you got it fixed. Take care and stay warm.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman Furnace ignition not occurring [ 8 Answers ]

Hello everyone, I have a GMP075-4 Goodman gas heating & air conditioning that comes on but no ignition occurs. I have done the minor troubleshooting process written on the instruction sheet but that didn't help. I turned off the power supply to the furnace and turned off the ignition switch and...

Goodman Furnace -takes 2 Or 3 Ignition Cycles before Stays Running [ 2 Answers ]

Hi,hope you can help me out.i have a goodman manufacturing forced air furnace that i believe is giving me a warning sign of a future failure.what has happened is in this order,1st one morning the thermostat showed that the furnace was on and it was'nt.turned it off and then back on at the...

Goodman mgmt090-3a no ignition [ 3 Answers ]

Got home last night no heater on, usually it's the pressure relay hose/metal housing intack with minteral buildup, checked all clear, turned on I hear gas coming on but no ignition, I test it 3 times after the third time finally get led light either blinking 1 time or constantly there's about a...

Goodman gmp075-4 problems [ 2 Answers ]

Problems with My goodman gmp075-4 furnace. The blower motor runs regardless of thermostat controls. The induction motor doesn't come on, unless The limit switch is unhooked... then she spins like a champ. I removed the induction assembly and cleaned it all out, including the flue. The trouble...


View more questions Search