    Goodman gas funace pressure switch problem
    I have a Goodman 93% efficient furnace that short cycles the gas burners. It cycles the vent on, starts the igniter, fires the burners and kicks on the blower but the burners only stay on for a short time ( less than 30 seconds). The led on the circuit board gives me 3 flashes indicating " pressure switch failure to close". The unit is venting properly and the hose from the venter to the pressure switch is not blocked. Any idea how I check the pressure switch or is there something else I need to check? I should also say that all this happens after the unit has been powered off and powered back on @ the circuit breaker and will run for several hours exactly as it should without said problem. Thanks
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Jan 30, 2007, 04:43 PM
    Is there a pipe for the combustion air ran outside? How old is it? Could there be water in the exhaust pipe or not enough fall back to the furnace? What BTU, sixe of pipe, length of pipe and how many elbows. I run into this all the time, installers push the envelope on the venting requirements.
    bdarnay's Avatar
    bdarnay Posts: 6, Reputation: 1
    New Member
     
    #3

    Jan 30, 2007, 05:31 PM
    16' of 2" PVC pipe with 2 elbows, the first elbow is at the lowest point and has the drain spigot running to the condensate pump that is working. The PVC runs to the outside of the house, is apporximately 10 years old, falls 3 inches back to the furnace in 12', not clogged and is definitely exhausting to outside of house (easy to see during the winter).
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Jan 30, 2007, 05:39 PM
    Check with a goodman supplier or the factory. I believe there were some problems with the pressure switch settings that would effect units as they get older. The fan does not put out enough for the switch to always activate
    OR just replace the switch.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #5

    Jan 30, 2007, 06:17 PM
    Is it on LP, is there soot in the vent pipe, (black)? And yes! Like hvac1000 said, it is not hard to believe a 10 year old pressure switch is bad.
    bdarnay's Avatar
    bdarnay Posts: 6, Reputation: 1
    New Member
     
    #6

    Jan 30, 2007, 07:18 PM
    Natural gas and there is no soot in the vent pipe.
    bdarnay's Avatar
    bdarnay Posts: 6, Reputation: 1
    New Member
     
    #7

    Jan 31, 2007, 08:23 AM
    One other thing I noticed today when I turned off the system to reset I could hear a sizzling sound coming from the secondary heat exchange. Could this be part of my problem?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #8

    Jan 31, 2007, 09:58 AM
    Is the drain open for the condensate water?
    bdarnay's Avatar
    bdarnay Posts: 6, Reputation: 1
    New Member
     
    #9

    Jan 31, 2007, 10:50 AM
    Drain is open and water is flowing from pump to drain
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #10

    Jan 31, 2007, 04:25 PM
    Quote Originally Posted by bdarnay
    Drain is open and water is flowing from pump to drain
    Ok from pump to drain... But it could be running slow from furnace to pump, the sizzeling sound makes me think there is too much water in the furnace.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman gas heater [ 9 Answers ]

I have a modelgmpn120-5 gas heater.. today I had gas company look at it.. it runs good for a while.. then shuts down... I go down take a black vacuum hose off.. it has water in it.. I empty it.. heater runs.. today the guy from the gas company said the secodary heat exchanger was bad... how much...

Goodman Gas Furnace [ 3 Answers ]

I have a Goodman Gas Furnace, the hot surface ignite will not come on nor the flame sensor. I have tried everything and I am fresh out of ideas. Could you please help me on this. Thanks

Goodman Gas Furnace [ 1 Answers ]

Up until yesterday my furnace was working fine now it does not come on at all. I have turned off the power to it and the breaker and still nothing. I also have tried turning on the air and that does not come on either. I don't know the model number but I have been using it for about 4 years now.

Goodman gas valve [ 2 Answers ]

I have a goodman model gmp 125-4. Last night I had a limit switch open code, I fixed it, the fan limit switch. Tonight I get a code 5 "false flame sensed", "gas valve stuck". I hit the valve with a scredriver handle, because I was told it might losen up the gunk sticking the valve. When I hit...

Gas valve pressure problem [ 1 Answers ]

I had an old Coleman Evcon furnace, the problem is when the flame came out doesn't come strong because the fleame stay right at the nozzle of valve pipe,


View more questions Search