Goodman Furnace Troubleshooting?

Asked Dec 28, 2011, 06:42 PM — 3 Answers
How can you tell if your heat exchanger is bad? I am getting high Co2 reading. And the flames seems to be blowing to strong, or could that be the gas valve, or dose it need adjustment in the tudes? I don't think the chinney is plugged.

3 Answers
mygirlsdad77's Avatar
mygirlsdad77 Posts: 5,539, Reputation: 1650
Plumbing Expert
 
#2

Dec 28, 2011, 07:33 PM
if you are getting high readings, and your vent is not leaking or restricted, then thats a pretty sure sign that your heat exchanger is bad. How old is the furnace? Do you notice a change in the flame when the blower kicks on? Where are you getting the strongest reading from, near the furnace, or at the supply registers? Is there a gas water heater in the same room as the furnace? Any other gas appiances in the home, and if so, what are the readings near them? Lots of options here, but dont take any chances. Make sure to turn off all gas appliances and use electric heaters untill the source is found.
Helpful  (1)
Joethehandyman's Avatar
Joethehandyman Posts: 2, Reputation: 10
Junior Member
 
#3

Dec 29, 2011, 11:09 PM
all it needed was a good cleaning with a wire brush and a shop vac. now the flames are nice and no co2 after retesting. thank you for your reply. it was the first time it was cleaned in aleast 10 years.
Helpful
mygirlsdad77's Avatar
mygirlsdad77 Posts: 5,539, Reputation: 1650
Plumbing Expert
 
#4

Dec 30, 2011, 02:05 PM
Good deal. Glad things went smoothly for you. And thanks for the update, I always appreciate that.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

goodman furnace troubleshooting? [ 3 Answers ]

I have a Goodman GDH 80703AXAC furnace it runs for about 30 min then shuts of on high limit then will allow relight? Any ideas what is going on?

Goodman furnace troubleshooting [ 7 Answers ]

My goodman furnace/ heat pump will not turn on when I turn on at AC the unit outside will turn on but the blower will not. There trouble shooting light is not on.

Goodman furnace troubleshooting [ 7 Answers ]

I put a new board in a GMP070 and the inducing fan motor kicks as normal, then the HSI starts to light but the whole board goes dead within 3 seconds.

Troubleshooting goodman furnace [ 1 Answers ]

The flame sensor keep burning out and only run for a couple of minute . Maybe the condensation trap is fully of dirt

Goodman furnace troubleshooting [ 2 Answers ]

I went away for a couple of days and returned to a cold house. I have a Goodman Model HCC075ND4R that has Electronic Ignition with Relay + VR80204 - S8600H Control. I can not get it to fully ignite. It tries to ignite over and over again. I see a single blue flame for a short time, but not main...


View more Heating & Air Conditioning questions Search