Question
 | |  | | | 
Nov 5, 2009, 05:42 PM
| | New Member | | Join Date: Nov 2009
Posts: 10
| | | Goodman furnace is making loud noise when in cool down mode. when the furnace fan is running in cool down mode, it sounds as if a flap on the exhaust vent is flapping in the wind | | | | | | |
Answers
 | |  | | |
Nov 5, 2009, 05:52 PM
|
#2
| | Ultra Member
Join Date: Aug 2007 Location: Cincinnati, Ohio
Posts: 2,051
| Sounds like you may have a clogged condensate trap, and the inducer housing is flooding. Follow the drain tubes from the inducer and secondary heat exchanger to locate the trap. Remove it and flush with water. This should be done every year prior to heating season, in addition to cleaning the flame sensor (consult HVAC1000 on this forum if you need a pic of sensor). |
| | | | | | |  | |  | | |
Nov 5, 2009, 06:21 PM
|
#3
| | Ultra Member
Join Date: Apr 2009 Location: West Virginia
Posts: 1,614
| where is the noise the loudest, and do you hear it clear upstairs? |
| | | | | | |  | |  | | |
Nov 5, 2009, 06:25 PM
|
#4
| | Ultra Member
Join Date: Aug 2007 Location: Cincinnati, Ohio
Posts: 2,051
| Quote:
Originally Posted by Joshdta where is the noise the loudest, and do you hear it clear upstairs? | It gets louder as she gets closer.  Sorry, couldn't resist... |
| | | | | | |  | |  | | |
Nov 5, 2009, 07:05 PM
|
#5
| | New Member
Join Date: Nov 2009
Posts: 10
| it is loud at the unit and it sounds like it is coming from inside the unit above the burners.
where is the condensate trap located? |
| | | | | | |  | |  | | |
Nov 5, 2009, 07:13 PM
|
#6
| | Ultra Member
Join Date: Aug 2007 Location: Cincinnati, Ohio
Posts: 2,051
| You didn't mention a model #, so...most likely located on the outer lower sidewall of the furnace. Usually black plastic with several hose connections and an outlet piped to a floor drain or pump. |
| | | | | | |  | |  | | |
Nov 5, 2009, 07:14 PM
|
#7
| | New Member
Join Date: Nov 2009
Posts: 10
| thanks! model GMP100-4 |
| | | | | | |  | |  | | |
Nov 5, 2009, 07:19 PM
|
#8
| | Ultra Member
Join Date: Apr 2009 Location: West Virginia
Posts: 1,614
| if the trap was that full of water the furnace would probally not fire |
| | | | | | |  | |  | | |
Nov 5, 2009, 07:22 PM
|
#9
| | Ultra Member
Join Date: Aug 2007 Location: Cincinnati, Ohio
Posts: 2,051
| Ok, I figured it was a GMPN when you mentioned an exhaust vent. GMP's don't have a condensate trap or secondary heat exchanger. How old is the unit? If you can post the serial # that will tell us. |
| | | | | | |  | |  | | |
Nov 6, 2009, 05:19 AM
|
#10
| | New Member
Join Date: Nov 2009
Posts: 10
| it is a 2000
i will look for the serial #
thanks |