Ask Me Help Desk

Ask Me Help Desk (https://www.askmehelpdesk.com/forum.php)
-   Heating & Air Conditioning (https://www.askmehelpdesk.com/forumdisplay.php?f=150)
-   -   Furnace gas valve operation (https://www.askmehelpdesk.com/showthread.php?t=295189)

  • Dec 23, 2008, 11:55 AM
    bigolt
    Furnace gas valve operation
    I have an older Dayton model 3E473A wall furnace that has a bad gas valve. Grainger no longer sells replacement parts for this furnace. I went on line and using the part no. of the existing bad gas valve (Robert Shaw 7000 AERB-5-S7C), I found a cross referenced replacement gas valve (GSV720402). My concern is that my furnace is rated at 40,000 input BTu's and the specs for the replacement gas valve says up to 150,000 BTU furnace. Does the burner control the amount of btu's or does the gas valve control the amount of gas to meet what the furnace is supposed to put out in heat?
  • Dec 23, 2008, 11:58 AM
    KC13

    Typically, the gas valve can be adjusted to the proper output pressure for the application. If the "up to" value was less than the application, output would be insufficient. Manifold pressure must be checked and adjusted to unit rating plate value after valve replacement.

  • All times are GMT -7. The time now is 12:16 AM.