    Furnace flame cuts out
    Having problems keeping flame burning in furnace.Oil furace hadn't been used in 2 years and had oil delivered recently.We figured the tank would be close to empty but were told after it was filled that it was already over 1/3 full. Furnace would light up with yellow flame but then turn blue and then safety kicked in. The furnace is making loud rumbling noises off and on but can't keep furnace going long enough to figure out anything.We've replaced nozzle,transformer,oil filter, cad cell and tested pump pressure so now we're wondering if the oil was bad from sitting in the tank for 2 years. Oil seemed a little on the thin side as well.Any Suggestions?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Nov 2, 2006, 08:46 PM
    I would take a look at the limit switches/temperature sensors. They are around the heat exchanger. The furnace is wired to shut off if the blower doesn't come on or if it overheats. A false signal from a dirty or failed sensor can shut down a properly working furnace. Does the blower come on?
    dougandrew's Avatar
    dougandrew Posts: 4, Reputation: 1
    New Member
     
    #3

    Nov 2, 2006, 08:50 PM
    Quote Originally Posted by dougandrew
    Having problems keeping flame burning in furnace.Oil furace hadn't been used in 2 years and had oil delivered recently.We figured the tank would be close to empty but were told after it was filled that it was already over 1/3 full. Furnace would light up with yellow flame but then turn blue and then safety kicked in. The furnace is making loud rumbling noises off and on but can't keep furnace going long enough to figure out anything.We've replaced nozzle,transformer,oil filter, cad cell and tested pump pressure so now we're wondering if the oil was bad from sitting in the tank for 2 years. Oil seemed a little on the thin side as well.Any Suggestions?
    I may be wrong but doesn't the burner have to heat up the heat exchanger for the blower to kick in? The flame doesn't seem to stay going longer than 10 seconds. The furnace is an older Intertherm if that helps.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Nov 2, 2006, 09:11 PM
    OK, there is a sensor that shuts off the oil if it doesn't detect flame. It will be right where the flame is.
    dougandrew's Avatar
    dougandrew Posts: 4, Reputation: 1
    New Member
     
    #5

    Nov 2, 2006, 09:16 PM
    So why would the flame keep dying out after only 10 seconds or so?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #6

    Nov 3, 2006, 05:23 AM
    This is a safeguard. If the oil doesn't ignite, you don't want it to continue to spray into the furnace. This thread describes how the flame sensors work, which may help you find it and the problem.
    https://www.askmehelpdesk.com/heatin...ons-39464.html

    If the flame sesor doesn't give a flame detected signal soon after the fuel comes on, the furnace shuts the fuel off quick before anything goes kaboom.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #7

    Nov 3, 2006, 05:54 AM
    You said you replaced the cad cell. (That is the flame sensor). Fuel oil is organic and bacteria and the like can grow in it, usually making it sludgy not too viscous. Are you shure the oil pressure stayed up where it needs to be? Sometimes the king coupling can be partly stripped out and start slipping. Also did you use the right nozzle, if you went off the old one it could have been wrong. Whoever you bought the parts off can look up the model number of the furnace to be sure, also give him the burner number. Hope this helps
    Airwren's Avatar
    Airwren Posts: 15, Reputation: 2
    New Member
     
    #8

    Nov 3, 2006, 06:15 AM
    Quote Originally Posted by dougandrew
    Having problems keeping flame burning in furnace.Oil furace hadn't been used in 2 years and had oil delivered recently.We figured the tank would be close to empty but were told after it was filled that it was already over 1/3 full. Furnace would light up with yellow flame but then turn blue and then safety kicked in. The furnace is making loud rumbling noises off and on but can't keep furnace going long enough to figure out anything.We've replaced nozzle,transformer,oil filter, cad cell and tested pump pressure so now we're wondering if the oil was bad from sitting in the tank for 2 years. Oil seemed a little on the thin side as well.Any Suggestions?
    I am not an oil expert, but did experience a similar problem. In my case there was no combustion air as I had sealed all the windows and doors. You could see soot building up on the joints of the exhaust. Once I supplied fresh air to the mechanical room all my problems stopped
    dougandrew's Avatar
    dougandrew Posts: 4, Reputation: 1
    New Member
     
    #9

    Nov 3, 2006, 10:19 AM
    Pump pressure stayed at 100 so it's not the pump,transformer has good arc, correct (new)nozzle for furnace. Coupler is fine. For some reason flame does not stay longer than 10 seconds.Any other suggestions?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #10

    Nov 3, 2006, 11:25 AM
    Even if the new flame sensor is working and sending the signal it should, it could be getting lost in the controls, either a bad control board, or a bad relay. Can you locate anything that clicks when the flame goes off?
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #11

    Nov 3, 2006, 03:18 PM
    Are you sure the primary air dampers on the combustion blower are open. If the flame seams to light good it should stay on. Do you have to reset the relay each time? Is the bottom of the heat exchanger full of oil?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Gas furnace - no flame [ 4 Answers ]

Hope someone out there can help, because it's going to get cold this weekend! I have a split HVAC unit with furnace in attic. Written on front of unit is Intertherm. Inside panel of unit says Nordyne, and the Ignition Control is Robert Shaw. The unit is 13 years old and the heat worked fine...

Old flame won't die [ 4 Answers ]

HI, I am, but not strongly, precognitive and an empath, however; when it comes to anything about myself I am clueless! So, I am hoping that a stronger psychic can tell me something. I dated a guy for a year and a half starting when I was 16. I know everyone's says it's "puppy" love at that...

Furnace Flame Sensor - Multiple Failures [ 2 Answers ]

Dear Experts, I have an ArcoAire RPJll furnace, vintage 1993 - natural gas. The furnace came with a 50A55-120 controller and a WR 760-470 flame sensor. Since installation the furnace has consumed 1 to 2 flame sensors a year and 3 controllers since installation. At present it has the 50A55-843...

Flame on! [ 4 Answers ]

Please HELP. I'm having a problem with my furnace rather it's my thermostat it's no responding to the temperature. I replcae it with a new one and it's still the same the second I turn power on the flame and fan blower turns on.What could it be. The wring it's only two wires. W and r.

Old flame? [ 1 Answers ]

I can't seem to get an old boyfriend out of my head. I think of him often even though I am with someone. I felt like we were like best friends. Things just didn't work out though. Any ideas? Will I ever see him again? Does he think of me? Or is this all in my head?


View more questions Search