    Furnace fan keeps blowing
    Carrier Furnace. My furnace blower stays on after shutdown. Keep getting a code 33 which says flame rollout switch is open. How do I bypass them or tell if they are bad? Had control board replaced afew months ago. If I let the system sit a couple of hours, it will usually reset. Please help.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Feb 15, 2007, 01:59 PM
    Roll-out switch's require a manual reset on the limit switch itself. If it is resetting itself it must be a bad switch or electrical connection, you might need a pro, the switch's are pretty cheap.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace sometimes blowing cold air [ 7 Answers ]

We bought a brand-new house in May 2002. This winter (I don't think it happened last winter) when it got really cold outside, the furnace blew cold air. When it warms up outside, it starts blowing warm again. We had someone come and look at it and he told us it had a 30 degree heat pump?? And when...

Furnace turns off heat and fan continues blowing cold air. [ 14 Answers ]

Carrier split unit Model 58RAV055-GC Circuit Board at Furnace CES0110057-00 Natural Gas I am experiencing a problem with my heat. I have a programmable zones thermostat and noticed that the air was not coming out hot when it was suppouse to be. The temperature was set to 75 but the temperature...

Furnace blowing cold air! [ 2 Answers ]

i have been experiancing problems with my furnace blowing out cold air, the first time i checked the code light it was working normal, the second time it was flashing continuosly fast and it meant call for heat, the third time i checked it said to replace the IFC!! i have no idea what the ifc is,...

Fuse in furnace blowing [ 4 Answers ]

My buddy has a payne heat pump system with a payne air handler and every time the heat is turned on at the termostat the fuse blows in the air handler cabinet. The fuse will not blow if emergency heat is turned on or the a/c what is the problem here? I have been working in hvac for six years but...

Why are Fusings Blowing Out when I Turn the Furnace On [ 1 Answers ]

About a month ago we replaced a heating coil in our water tank and now we started to use the furnace something is causing the fuses to blow out every time we turn the furnace on . Can anyone give me some advise on what to checkout or what to do? :confused:


View more questions Search