    Furnace Blower stays on, no heat
    Hello, I have an older Bryant furnace model # 396gadd36075. I turned on the heat the other day and the no heat. I notice the unit had been turned off (pilot was not lit), apparently by the service company I use when they came to do the spring check for the AC. I followed the instructions to re-light the pilot and turned the unit on. The result was the blower kicked in but the burners still won’t lite. Now the blower stays on and the thermostat is not working at all. Could this be a gas valve or thermostat problem maybe? How can I reset the unit? Thanks.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #2

    Oct 31, 2007, 06:51 PM
    Turn off the power,, jumper th red and white stat wires together,, at the furnace or unhook from the stat and jumper them together,, turn power back on if fornace goes through the paces and works,, I`d consider the stat is the problem,
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #3

    Oct 31, 2007, 07:19 PM
    The first thing to do is to see if you have the control 24 volts. This is best done by checking the terminals of the transformer with a volt meter. Otherwise, if the above results in the furnace running, you have the voltage. If the blower just runs, either the transformer is dead, or the fuse protecting it is blown. On an older furnace, likely such would b an inline one. You can find a picture of one at https://www.askmehelpdesk.com/heatin...ons-58313.html If you don't have a fuse, and the transformer is shot, I would strongly suggest installing a fuse. Otherwise, your new transformer could die in a cloud of smoke as soon as you turn the power back on.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace blower on - no Heat [ 20 Answers ]

I have a Carrier furnace with an automatic ignition. The fan is constantly running but it is not heating. Additional Information: Model 58PAV: The Red Led Status light is rapidly flashing - which according to the manual means 'Line voltage (115VAC) polarity reversed. If twinned, refer to...

Blower won't run in auto for heat with oil furnace [ 9 Answers ]

I have an oil furnace. A/C works fine. Heat last season worked fine. Started up furnace this year just fine. But blower would not start on auto. The blower will run in heat mode when set to On. I replaced the Limit Switch in the Plenum. No change.

Furnace fan blower stays on too long. [ 1 Answers ]

The fan blower for a coleman mobile home furnace stays on and begins to blow cold air before shutting off, how do I know if the fan/lower limit switches are the right ones? Model # 7680C856 80,000 BTU.

Heat won't come on and blower stays on all the time. [ 1 Answers ]

I have a problem with a furnace that the heater won't come on, "not at all", and the Blower it stays running all the time, can't turn it off unless disconnected. Before replacing the Circuit Board, I will appreciate if somebody tells me what other reasons are there that may cause this problem. ...

No heat, blower runs constantly, carrier gas furnace [ 7 Answers ]

This am we I got up the blower on my carrier series 100 gas furnace (approx 10 years old)was running and blowing out cold air. Even with the thermostat turned to off the blower runs constantly. The only way to stop the blower from running is to turn the switch on the side of the furnace to off or...


View more questions Search