Question
 
 
#1  
Old Oct 30, 2007, 03:42 PM
thale4314
New Member
thale4314 is offline
 
Join Date: Oct 2007
Posts: 6
thale4314 See this member's comment history on his/her Profile page.
Fan runs forever when in heat mode but not in ac mode

Great web site and concept!!! I have a York forced air gas furnace that has a Honeywell Fan Limit switch. The unit works great in the summer. The ac and the fan shut off correctly. However, in the winter the heat will reach its temp setting and turn off but the blower continues forever. I have learned from trial and error that if I wait a few minutes to let the unit cool down, then I can lightly touch the Honeywell fan limit switch dial and the fan will cut off. If I do not do this, then the fan runs forever. It is really odd. Hope someone has some ideas. I am about to put my house on the market to sell and I would like to get this fixed so it won't be an issue for prospective buyers or inspectors. Thanks, Terry

Reply With Quote
 
     

Answers
 
 
Old Oct 30, 2007, 05:09 PM   #2  
Senior Member
T-Top is offline
 
Join Date: Nov 2006
Posts: 973
T-Top See this member's comment history on his/her Profile page.
It sounds to me you found your problem with out any help. If the switch is sticking all the time you need to go ahead and replace it. One thing you might try is adjusting the blower off setting on the control to a higher temp to see if it will kick off then. Good luck.
  Reply With Quote
 
     
 
 
Old Oct 31, 2007, 06:50 AM   #3  
New Member
thale4314 is offline
 
Join Date: Oct 2007
Posts: 6
thale4314 See this member's comment history on his/her Profile page.
Quote:
Originally Posted by T-Top
It sounds to me you found your problem with out any help. If the switch is sticking all the time you need to go ahead and replace it. One thing you might try is adjusting the blower off setting on the control to a higher temp to see if it will kick off then. Good luck.
Thanks T-Top. I adjusted the OFF setting a few degrees higher and now it seems to be working. I did not have time to test several times to make sure it is working consistently, but I will tonight. Thank you very much for your help and especially your quick response. This is a great concept. Hope I can help someone at some point.
  Reply With Quote
 
     

Bookmarks


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
maytag neptune dryer does not heat in normal mode edmundja Appliances 2 Mar 30, 2008 02:19 PM
Whirlpool dryer only runs fabric guard mode thesauceman Appliances 0 May 23, 2007 08:03 AM
heat pump stuck in heat mode bectroy Heating & Air Conditioning 4 Mar 22, 2007 02:04 PM
Furnace turns off at 'ON' mode and will not operate at 'AUTO' mode spanky28 Heating & Air Conditioning 6 Jan 23, 2007 06:01 PM
Furnace turns off at 'ON' mode and will not operate at 'AUTO' mode spanky28 Heating & Air Conditioning 2 Jan 10, 2007 11:17 AM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 01:49 PM.