    Dual Zone Heating
    I have forced hot air dual zone heating at my home. When I set the temperature at 70 in the first floor.. The fan is also blowing in my 2nd floor and the temperature increases in the 2nd floor to 70. Where as the thermostat in the second floor is set to 62.

    I looked at the furnace and saw a light near the 2nd zone saying closed.

    When I set the temperature in the second floor to 70 and set the first floor temperature to 62. It looks like only the 2nd floor is being heated and the light on the furnace to the 2nd zone say Open.

    Is this common or is there something wrong with the furnace.. We had our house built 2 years ago.. So the furnace and the other things are new.

    Thanks
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Apr 22, 2006, 12:21 PM
    Sounds as if the second floor damper is not getting signal to close. Each operation of the damper needs a control voltage to open and close, and seems there is a switch or relay not closing contact. This may be hard to find as it sounds as if you have a master control panel.

    Best you can do is to trace the wiring from the damper motor, here you should find three wires, usually back red white, either the black or red may be for open or close. Once you trace back to a relay or switch, test the relay for coil voltage to make it operate, and test the continuity of each contact.

    One contact is to close the damper, the other to open.
    gautamanne's Avatar
    gautamanne Posts: 9, Reputation: 2
    New Member
     
    #3

    Apr 22, 2006, 07:42 PM
    Thanks for the info.. I was able to set the Dampner to manually close, I think it's the dampner circuit with is busted... I will need to replace this professionally

    Thanks for the help

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Zone valve problem [ 5 Answers ]

Zone valve for upstairs will not open. Already replaced thermostat. The only time I have heat upstairs is when the valve in manually opened and the downstairs heat kicks on. Any help or advice would be great! Thank you.

Zone Alarm Firewall [ 7 Answers ]

I am running Windows XP Home with Internet Explorer. For PC Protection I AVG Free Anti-Virus, Ad-Aware SE to detect and rmove Adware, Microsoft Anti-Spyware,Spybot,and Spyware Blaster to detect and remove spyware.Do you advise me to also download Zone Alarm Firewall protection. Some say yes and...

Zone valves [ 2 Answers ]

Looking for a wiring diagram for a new dunkirk boiler . Just the diagram for the 3 zone valves. Company says that the boiler transformer is enough to run three zones ( 24v) . Or do I need to add transformer. Just can't figure out the wiring from one zone valve to another. Contacts on each zone are...

Wiring a 2nd zone [ 1 Answers ]

Central a/c is all set up on my finished basement as a 2nd zone. In the upstairs hall closet, I can see a large round pipe running down from the attic to the basement. Ceiling ductwork and vents in the basement are all connected to it. There is a programmable thermostat in the basement as well. The...


View more questions Search