    p122654's Avatar
    p122654 Posts: 3, Reputation: 1
    New Member
     
    #1

    Feb 19, 2012, 03:07 AM
    Cycle circuit breaker to start Coleman Electric
    Thermostat indicates that heater should be turning on. Circuit breaker has power, tested it. Cycling one of two circuit breakers starts Coleman Electric heater operation. Sometimes this will cause heater to work for days. Then out of the blue the house gets cold and the breaker has to be cycled again. Could it be a week low voltage transformer or one of the relays I should be testing?
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #2

    Feb 19, 2012, 07:36 PM
    It sound like you have a heat sequencer going bad(if it all electric and not a heat pump). The sequencer times on and off the heat strips and blower. Technically it's a time delay relay.
    p122654's Avatar
    p122654 Posts: 3, Reputation: 1
    New Member
     
    #3

    Feb 19, 2012, 10:28 PM
    That is what I was thinking but a low voltage transformer that is not outputting the correct or a lower voltage that the relay might need to start the sequence when receiving a bust of energy (cycled CB) will set it off on it's way. I'll attack the relay's first then.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Cycle circuit breaker to start Coleman Electric [ 0 Answers ]

Have a 30 year old Coleman Electric. Thermostat is flashing indicating relay (energy efficient) closed. Cycling one set of two 30 amp circuit breakers get the furnace running again. The dual breaker does not feel like it is tripped. But maybe one side could be tripped. Was thinking about changing...

Electric stove circuit breaker? [ 5 Answers ]

I have a 240Vac Stove 4 prong outlet. The wiring to the receptacle is fully installed. Stove not working properly. I pulled out my meter and I measure 120 from L1 to Ground and 120 from L2 to Ground, I measure 0V between L1 and L2. How can I correct this to 240 between L1 and2?

Circuit breaker tripping on electric well pump [ 9 Answers ]

I have an electric well pump which trips the circuit breaker. The pump does not seem to work. I can reset the breaker but it trips again after five minutes or so. Do I have a pump problem or an electrical problem?

Coleman Electric Breaker - Keeps going off [ 1 Answers ]

I have a Coleman 3300L823 (23Kw /78,000 BTU) furnace and every 4 or 5 hours the lower circuit breaker goes off. Once I reset the breaker, it works for several hours and then goes off again. The weather has been very cold these last couple of days and I am wondering if it has anything to do...

What size circuit breaker does electric dryer need [ 0 Answers ]

What size circuit breaker does a electric dyer need


View more questions Search