    johnjjacks's Avatar
    johnjjacks Posts: 2, Reputation: 1
    New Member
     
    #1

    Sep 25, 2007, 08:35 AM
    Correct wiring for a thermostat
    Installing a new Honeywell thermostat to a Carrier system . Old thermostat was already removed before I got there. Wires from the wall are Red,Blue,White,Yellow and Grenn. Thermostat terminals are RH,RC,W,Y,G. I currently have it rigged up as follows

    Red to RH
    Blue to RC
    White to W
    Yellow to Y
    Green to G

    Only the AC works in this configuration, no heat.. What have I done wrong?

    Thanks for anyone that can help..
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Sep 25, 2007, 01:48 PM
    Hope this helps. https://www.askmehelpdesk.com/heatin...tml#post268211
    johnjjacks's Avatar
    johnjjacks Posts: 2, Reputation: 1
    New Member
     
    #3

    Sep 25, 2007, 01:55 PM
    Quote Originally Posted by johnjjacks
    Installing a new Honeywell thermostat to a Carrier system . Old thermostat was already removed before I got there. Wires from the wall are Red,Blue,White,Yellow and Grenn. Thermostat terminals are RH,RC,W,Y,G. I currently have it rigged up as follows

    Red to RH
    Blue to RC
    White to W
    Yellow to Y
    Green to G

    Only the AC works in this configuration, no heat.. What have I done wrong??

    Thanks for anyone that can help..
    So , if I understand , take the blue off RC , and leave it out , and use a jumper across RH /RC?
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #4

    Sep 25, 2007, 07:58 PM
    That is most likely correct. Open the furnace and see if blue is connected to anything.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #5

    Sep 26, 2007, 07:03 AM
    And as a post:

    Don't you mean disconnect red and (jumper RH to RC and connect to blue)?

    Since Cooling works, blue must be correct since it's connected to Rc. Red hopefully doesn't go anywhere. Red should normally be connected to R or (Rh and Rc), but since heat doesn't work something is amis or miswired.

    Blue might be second stage cooling, but since heat doesn't work and it's connected to red, this doesn't make sense either.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #6

    Sep 26, 2007, 09:25 PM
    No I mean connect red to RC and RH, blue is probably nothing but just in case I asked him to find out what it (blue) was connected to on the PC board or in the furnace. I won't stoop to berating your last post.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Matching up the correct capacitor with the correct condenser fan motor? [ 4 Answers ]

How crucial is it to match the right capacitor to the right condenser fan motor? If you have the wrong capacitor, can this cause the motor to stop after running for a while, say 20 or 40 minutes? It would start up again, but would allways stop. The specs for the motor are: Emerson E-line, model no...

Not sure about correct wiring [ 1 Answers ]

Appreciate any help here: I'm drawing my source from a kitchen light. This set of wires continues to a junction box in my attic. This junction box has four separate wires leading into it. One from the source that I just described. Two other wires lead to separate switches in the kitchen (one of...


View more questions Search