    Comfortmaker GUA Furnace forced draft fan runs constantly
    The furnace is a 1989 Comfortmaker GUA Series gas furnace with a White Rodgers Model 58E47-148 Hot Surface Ignition Module. With the burners unlit, the forced draft fan runs all the time. The LED light blinks constantly, which the information that came with the furnace says means "External Failure (Ignition lock-out)". It seems the cycle can be re-set by turning off the thermostat (or the furnace) and then turning it back on. It will go through the following cycle... the forced draft fan comes on immediately, there is a click, the igniter glows, the burner flames come on, there is another click, then the flames go out. It repeats this three times, then the ignitor does not come on anymore and the LED starts blinking and the draft fan stays on.

    Sometimes the furnace will work fine for several days, then the house gets cold, and I can hear the draft fan blowing. I turn it off and on, and everything is fine for an hour, or maybe several days. This has been going on since late last winter. Today, it took three or four re-starts to get it going. I have had our furnace guy out three times, and he says it is working fine when he is here. Any suggestions?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 30, 2008, 11:16 PM
    Quote Originally Posted by Jim37762 View Post
    The furnace is a 1989 Comfortmaker GUA Series gas furnace with a White Rodgers Model 58E47-148 Hot Surface Ignition Module. With the burners unlit, the forced draft fan runs all the time. The LED light blinks constantly, which the information that came with the furnace says means "External Failure (Ignition lock-out)". It seems the cycle can be re-set by turning off the thermostat (or the furnace) and then turning it back on. It will go through the following cycle...the forced draft fan comes on immediately, there is a click, the igniter glows, the burner flames come on, there is another click, then the flames go out. It repeats this three times, then the ignitor does not come on anymore and the LED starts blinking and the draft fan stays on.

    Sometimes the furnace will work fine for several days, then the house gets cold, and I can hear the draft fan blowing. I turn it off and on, and everything is fine for an hour, or maybe several days. This has been going on since late last winter. Today, it took three or four re-starts to get it going. I have had our furnace guy out three times, and he says it is working fine when he is here. Any suggestions?

    Try cleaning the flame sensor that can cause the problem you are having. It is the easiest item to do for starters. Post back with results.
    Attached Images
     
    Jim37762's Avatar
    Jim37762 Posts: 4, Reputation: 1
    New Member
     
    #3

    Dec 2, 2008, 06:25 AM

    So far, so good. I cleaned the sensor about 8:00 last evening and the furnace has worked since then. Thanks a bunch for the quick answer! BTW, my sensor is the straight one, not the angled one.

    Jim
    Jim37762's Avatar
    Jim37762 Posts: 4, Reputation: 1
    New Member
     
    #4

    Dec 2, 2008, 06:28 AM
    Also, while I had the power off to the furnace, I took off the sensor connection to the module and put it back on, just in case the contact at the connectors degraded.

    Jim
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Dec 2, 2008, 06:37 AM
    Glad you got it going. The sensor pictures are just to give a general idea as to what to look for.
    Jim37762's Avatar
    Jim37762 Posts: 4, Reputation: 1
    New Member
     
    #6

    Dec 4, 2008, 06:32 AM

    It is now Thursday morning, I cleaned the sensor on Monday evening and it is still working like it should. Again, thanks for the quick response! I think my issue is fixed.

    Jim
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #7

    Dec 4, 2008, 08:26 AM
    No problem. I am glad you got it going.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Inducer (Draft) Motor constantly on - Lennox UHG80-100 [ 3 Answers ]

My furnace's draft motor never stops even after one full heating cycle, which it's supposed to stop! This causes the pressure switch to stay closed even after the thermostat calls for heat the second time (after the initial heat cycle). When I stop and start the main switch in my basement,...

Forced hot air issue (Draft inducer fan) [ 1 Answers ]

My draft inducer fan is running for about 3 minutes before the furnace ignites. Once it ignites,the furnace is operating correctly. This seems to be longer than normal. Any ideas on what's wrong, or what I need to check/test? Thanks!

Lennox G12 furnace runs constantly [ 3 Answers ]

Furnace runs constantly and gets quite HOT, even if thermostat doesn't call for heat. Changed thermostat, didn't help. Removed new thermostat and checked to see if thermostat wiring had spark, it didn't. What now? I recently vacuumed unit. Does that matter? It ran fine for a few weeks following...

Draft fan runs always [ 1 Answers ]

Induce draft fan is on all the time, What can I check so that it will operate the right way?:p

No heat, blower runs constantly, carrier gas furnace [ 7 Answers ]

This am we I got up the blower on my carrier series 100 gas furnace (approx 10 years old)was running and blowing out cold air. Even with the thermostat turned to off the blower runs constantly. The only way to stop the blower from running is to turn the switch on the side of the furnace to off or...


View more questions Search