    Coleman electric furnace
    I have a Coleman electric furnace in a mobile home. The furnace element turns on and heats up with the thermostat turned down to 50 degrees and with the inside temperature at 68 degrees. The thermostat doesn't click for the blower to turn on until I turn it up past 70 degrees. Why is the element heating up and then after it gets so hot the element turns off. It does this cycle about every two to three minutes. I have pulled the breaker to keep it from running but I would like to have heat. Any suggestions as to what part needs replaced.
    acetc's Avatar
    acetc Posts: 1,004, Reputation: 79
    Ultra Member
     
    #2

    Oct 12, 2007, 04:54 PM
    Does your fan run if you set the fan switch to "on" on the thermostat? Has your thermostat been replaced recently and if so did you have this problem before?
    The fan should come on immediately when you turn the thermostat down. Mike
    worshamr's Avatar
    worshamr Posts: 3, Reputation: 1
    New Member
     
    #3

    Oct 16, 2007, 05:17 AM
    My Coleman furnace still has the original equipment and thermostat. The thermostat doesn't have a switch to turn the fan to the on position. However, there is a switch to turn the fan on located inside the furnace cover. When I turn it on the blower runs. Also, when I turn the thermostat up past 70 degrees the element heats up and the blower kicks on like it is supposed to do and turns off when it reaches the appropriate temp. The element will continue to cycle and heat up even though it doesn't need to.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Electric Coleman Mobile home furnace [ 6 Answers ]

The blower fan keeps running and will stop until the breaker is shut off for a while. It may run fine through its complete cycles for a day or two, but will do it again! The furnace hasn't been used for about 4 years. What needs fixed or replaced, and where do I find these parts? The trailer was...

Coleman Evcon Electric Heat/Air unit filter placement [ 7 Answers ]

We live in a rented mobile home in Texas; the landlord requires us to change filters once a month in the heat/air unit, which is a Coleman Evcon. (There is no model number visible.) The filters were sitting tilted along the side, inside the case, when we moved in. We have lived here over a year and...

Coleman electric furnace fan runs only in manual [ 2 Answers ]

I have a mobile with a forced air Coleman electric heat. The fan will not run in the auto setting (switch by motor in cabinet) but the element will heat up. In manual the fan runs constantly and heat comes on with the thermostat. The heating company recently replaced the sequencers and said we...

Coleman Presidential electric furnace [ 2 Answers ]

The blower fan on my electric furnace will not shut off without tripping the main breaker switch. It is an older furnace that had not been used all too often as I generally use a wood/coal stove for heating, but had been operating properly when I have used it. The last time it was used , the...

Coleman Furnace [ 1 Answers ]

Burner will not stay light. Fan comes on, ign. Box activates, ign. Comes on, gas sol. Opens, Flame for 2-3 sec. ign. Box de-activates and drops gas sol. Ignitor after hot reads 40 ohms, cooling off as high as 170 ohm. Replaced: Ignitor box Gas sol. Blower PC Furnace was flooded with...


View more questions Search