Central AC blowing warm air, outside unit not running

Asked Sep 12, 2008, 09:58 PM — 3 Answers
My question is the following:

My inside central AC is blowing warm air. I've checked the thermostat, its ok, I've checked the breaker and that seems ok. This started after a power outage that we had about 2 weeks ago and my unit outside does not run when the inside unit is running. In fact, the outside doesn't run at all. I pulled the fuse/breaker and reinserted, still nothing.

It was installed brand new in 2004, $5000, its and American Standard/Trane, any suggestions as to what could be wrong..before I spend a ton of money on a service visit, its a $100 here.

Thank you so much, fans just don't do it here

Karen

3 Answers
hvac1000's Avatar
hvac1000 Posts: 14,539, Reputation: 2381
Heating & Air Conditioning Expert
 
#2

Sep 13, 2008, 06:37 AM


pulled the fuse/breaker and reinserted, still nothing.

Did you test the fuses if fuses are present?
Helpful
mygirlsdad77's Avatar
mygirlsdad77 Posts: 5,542, Reputation: 1650
Plumbing Expert
 
#3

Sep 13, 2008, 02:19 PM
Are your themostat wires exposed outside? If they are check to see that they haven't been damaged. If they aren't, go to your furnace and find where the thermostat wires connect to the board. Jumper terminals are and why and see if the unit comes on outside
Helpful
EPMiller's Avatar
EPMiller Posts: 623, Reputation: 188
Senior Member
 
#4

Sep 13, 2008, 03:08 PM
I apologize for my comment (now edited out). I was confusing 2 posts.

First verify you have 240 volts out at the ODU (outdoor unit) disconnect box. Then get someone to get the tstat to call for cooling while you listen at the ODU. You should hear the contactor pull in. If the contactor pulls in, then the tstat signal is getting there. If it doesn't, then maybe the contactor is bad. Or the low voltage supply. Or something at the IDU.

If that happens then listen for humming. If not then maybe the contactor contacts are bad. Or the capacitor(s) is bad. I think this one has a control board which could be bad also. Is the compressor (the big metal canister down in the center) running? Does the fan on top run? If one or the other isn't running then you've at least isolated the problem to that part.

I could go on, I've only scratched the surface of troubleshooting. I still didn't touch the IDU, but you get the picture. On these systems you might just have to call for service. Unless you have the tools, are good at reading schematics and know what is supposed to be happening and when. At least you did a couple of elementary checks and know more now than when you started. Congratulations.

EPM
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

My AC unit is blowing warm air, how do I fix it? [ 12 Answers ]

Is there a way to fix my AC Unit without calling a technician?

Central Air blowing warm air [ 2 Answers ]

My central air is running inside but it is only blowing out warm air. The outside unit is not running what so ever. Any idea's, maybe a switch needs to be replaced?

AC unit blowing warm air [ 5 Answers ]

First the fan would not stop running in auto position or if unit turned off. Now fan is still running but AC is not cooling air. Outside fan is running. How can I check if relay switch is bad? Or where do I check outside on fan unit if compressor(?) is bad? I need to be told where to look for these...

Air Handler Blowing Warm Air/Outside Unit Humming Only [ 4 Answers ]

We came home yesterday to a 90 degree house. It was 95 degrees here yesterday and my husband left the setting at 72 degrees all day. I'm not sure if this had anything to do with the problem, but we thought it may have frozen/overheated the Carrier system (approx. Five years old) during the heat...

AC is running but blowing out warm air [ 8 Answers ]

My A/C is running outside but its blowing out warm air its not cooling. What is the problem


View more Heating & Air Conditioning questions Search