    Carrier furnace error code 33
    I have a Carrier furnace that displays error code '33'. Carrier only provides the answer to service personnel. What does this code mean as my furnace keeps going out?
    -sincerely, getting cold.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 24, 2008, 09:45 AM
    Look on the back of the furnace blower door. There is a drawing there with the codes listed. Since you did not take the time to post the model number of your unit I used my crystal ball to find what 33 means for you.

    33 LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will
    run for 4 minutes or until open switch remakes whichever is longer. If open
    longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes
    status code #33 continues to flash until blower shuts off. Flame rollout switch
    requires manual reset. Check for: - Restricted vent
    - Proper vent sizing - Loose blower wheel - Excessive wind
    - Dirty filter or restricted duct system.
    - Defective blower motor or capacitor. - Defective switch or connections.
    - Inadequate combustion air supply (Flame Roll-out Switch open).

    You can try to resaet power THEN push the little reset buttion. Here is a generic manual for Carrier

    http://www.xpedio.carrier.com/idc/gr.../58mxa-9sm.pdf

    You might have to call for On Site professional service since according to the diagram it could be multiple items in the failure.
    axe11111111's Avatar
    axe11111111 Posts: 1, Reputation: 1
    New Member
     
    #3

    Sep 25, 2012, 11:39 AM
    It's possible that the AC indoor coils might be clogged which restrict air from flowing out of the furnace and causing it to heat up excessively. Look into cleaning the coils which usually sits above the furnace.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Sep 25, 2012, 11:58 AM
    It's possible that the AC indoor coils might be clogged which restrict air from flowing out of the furnace and causing it to heat up excessively. Look into cleaning the coils which usually sits above the furnace.

    YES

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Error code 14 - Carrier Weathermaker 8000 [ 4 Answers ]

I've cleaned the flame sensor after days of ups and downs into my attic. I'm wondering if there is a reset switch that I need to trip. My steps were 1) unplug the power source, 2) remove covers, 3) turn off gas control switch 4) clean flame sensor with steel wool and 5) reverse through the...

Carrier 8000 Error Code 21 [ 9 Answers ]

Hello all, I have read through many post but can not find info on an error code 21. Any idea which direction I need to go with fixing this unit? Unit says 21 is a Gas Heating Lockout or Stuck gas valve relay. Does this mean I need to get a hammer and tap on that thing to unstick it? :D Any Help...

Code 54 on carrier weathermaker furnace [ 1 Answers ]

My furnace stopped working today. It is a weathermaker (carrier) 8000 That is approx 14 years old. It has been serviced regularly To the best I can tell it is flashing a code 5 4 can anyone help me with this? It kicks on, blows cold air for a few minutes then shuts down. Thank you

Where to start with error code 14, Carrier 8000ts [ 21 Answers ]

Hi, newbie here. Got a 4.5 year old Carrier 8000TS. Noticed the heater wasn't working, saw the error code was 14. After I turned power off and then on to the furnace, I turned the thermostat to heat again. The furnace made noise, but the blower didn't turn on. I noticed there was a faint...


View more questions Search