Is capacitor specific to fan motor?

Asked Jul 5, 2011, 07:56 AM — 5 Answers
I am replacing my AC fan motor and the site recommends changing the capacitor at the same time. Do I need to do this or if my exisiting capacitor still works or should I just leave it? If I do need to replace it, the model # I currently have is no longer produced. Do I just get the capacitor that is recommended by the site where I am ordering the fan motor?

5 Answers
Dr1757's Avatar
Dr1757 Posts: 194, Reputation: 132
Junior Member
 
#2

Jul 5, 2011, 08:14 AM
It's pretty much standard practice to replace the capacitor when you replace the motor. There's a good chance there is nothing wrong with the capacitor currently installed. When replacing a capacitor it has to be the same rating as the one being removed. If the store you're buying the motor from recommends a particular size capacitor your safe going with it.
Helpful  (2)
JayBrads's Avatar
JayBrads Posts: 6, Reputation: 10
Junior Member
 
#3

Jul 5, 2011, 08:26 AM
The new one is Carrier 370V, 35/5 MFD and the old one is Dayton 440VAC, 40/5MFD. The motor model # is HC39GE237. The website I am purchaing the motor from said to use the Carrier capacitor listed above. The ratings don't seem to be the same. Should I do something different?
Helpful
JayBrads's Avatar
JayBrads Posts: 6, Reputation: 10
Junior Member
 
#4

Jul 5, 2011, 08:40 AM
Comment on Dr1757's post
Quote:
Originally Posted by Dr1757 View Post
It's pretty much standard practice to replace the capacitor when you replace the motor. There's a good chance there is nothing wrong with the capacitor currently installed. When replacing a capacitor it has to be the same rating as the one being removed. If the store you're buying the motor from recommends a particular size capacitor your safe going with it.
The new one is Carrier 370V, 35/5 MFD and the old one is Dayton 440VAC, 40/5MFD. The motor model # is HC39GE237. The website I am purchaing the motor from said to use the Carrier capacitor listed above. The ratings don't seem to be the same. Should I do something different?
Helpful
mygirlsdad77's Avatar
mygirlsdad77 Posts: 5,539, Reputation: 1650
Plumbing Expert
 
#5

Jul 5, 2011, 04:25 PM
These are dual capacitors, the 35 and forty signify the compressor side, and the 5 is for the fan. If you use the new cap, you will be using the wrong size for the compressor. Either keep the old cap and only use the herm (compressor side), and get a separate 5mfd for the fan, or get the correct dual cap which would be just like the old one, except it would be, well, new.
Now, that being said, if you actually had the old cap tested, and it is indeed within range, then you are probably safe reusing it. I always replace caps when changing motors, but that's because I have to warranty my work, and its just a good practice for a professional. Capacitors are fairly cheap and easy to replace. I have seen people replace a motor, only to find out it was just a five dollar cap that was bad. Now that hurts.
Helpful  (1)
JayBrads's Avatar
JayBrads Posts: 6, Reputation: 10
Junior Member
 
#6

Jul 5, 2011, 04:50 PM
Comment on mygirlsdad77's post
Quote:
Originally Posted by mygirlsdad77 View Post
These are dual capacitors, the 35 and forty signify the compressor side, and the 5 is for the fan. If you use the new cap, you will be using the wrong size for the compressor. Either keep the old cap and only use the herm (compressor side), and get a separate 5mfd for the fan, or get the correct dual cap which would be just like the old one, except it would be, well, new.
Now, that being said, if you actually had the old cap tested, and it is indeed within range, then you are probably safe reusing it. I always replace caps when changing motors, but that's because I have to warranty my work, and its just a good practice for a professional. Capacitors are fairly cheap and easy to replace. I have seen people replace a motor, only to find out it was just a five dollar cap that was bad. Now that hurts.
Thanks. I guess I ordered the wrong capacitor. It has not shipped yet, so I should be able to change it in the AM.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Outside fan motor bad or capacitor? [ 16 Answers ]

I came home late and found the house warmer than should be, looked at thermo and its set for 74 but reads 81 , so I go to vent its blowing room temp. So outside next to find the fan not spinning,I shut off ac inside and g back to outside unit . As I was trying to find the problem I smelled the fan...

AC Fan Motor, capacitor, or what? [ 9 Answers ]

I had the fan motor of my outdoor AC unit replaced about 5 years ago, it has an AO Smith mod F48K92A01 which I found online for about $65 but want to make sure it is not possibly the capacitor or something else first. I caught the unit having the fan hitting the splicer near the top, clank,...

New fan motor new capacitor motor burned up [ 2 Answers ]

Air went out. Replaced outside motor fan and capacitor and it burned up again. Fan was very hot when I took it out. Causes?

How to hook a ac fan motor to a capacitor [ 3 Answers ]

I replaced my ac fan motor my original had three wires purple,brown and black,the new motor has 4wires yellow,black,brown,and brown white. I have a dual capacitor that has common,herm and fan how do I connect the wires to the capacitor.

Condenser fan motor or capacitor [ 5 Answers ]

I noticed my outside unit buzzing the other day, and the fan was not running. The unit is about 7 years old. I changed the capacitor yesterday, and the unit worked for about 5-10 minutes, but then shut down again with the fan stopping and the buzzing again. I'm 99% sure the buzzing is coming...


View more Heating & Air Conditioning questions Search