    A/C won't shut off once desired temp is reached
    I recently changed out my old mercury thermostat to a Honeywell RTH3100C digital non-programmable thermostat.

    The issue I'm having is that once the desired temperature is reached on the thermostat the a/c won't shut off. What could be the issue?:(
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #2

    Jun 18, 2009, 06:00 PM

    Did this problem start as soon as you put in the new thermostat? If so you probably have a wire in the wrong place.Tell us how you wired the new stat and we will try to help.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #3

    Jun 18, 2009, 07:38 PM
    If the problem started after changing the thermostat out, you have it wired wrong or programed wrong. If the problem was before changing out the t-stat, you got problems with the equipment. Like letmetellu said if you can give us more info it will help us. We promise not to bite.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Jun 18, 2009, 08:46 PM
    Quote Originally Posted by T-Top View Post
    We promise not to bite.
    You're no fun anymore... :p
    madivelle's Avatar
    madivelle Posts: 2, Reputation: 1
    New Member
     
    #5

    Jun 19, 2009, 06:45 AM

    The original t-stat was wired as such:
    Y - Yellow wire
    G - Green Wire
    R- Red Wire
    O - Orange Wire
    W2 - White Wire
    E - Black Wire
    C - Blue Wire

    This is exactly the way I wired my new Honeywell t-stat. The new one I bought has 9 wiring section whereas my old one only as 7 so the only two on the new t-stat that don't have a wire running to it is the "B" section and "L". Please help
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #6

    Jun 20, 2009, 10:05 AM
    Sounds like the new t-stat isn't multi-stage, so we'll throw that idea out... did you check the installation instructions for additional setup options? Maybe something isn't configured correctly. The "B" and "L" terminals are likely not needed for your system. Try this: set the system selector to "OFF" and the fan selector to "ON". Feel the air blowing from the registers - is it "room temperature" or does it feel "lukewarm"? Perhaps your auxiliary heater is powered for some reason...

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

My heat won't stop when desired temperature reached [ 1 Answers ]

Hi, I have 5 electronic zones, each with a separate thermostat, running off a single circulator motor. Two of my zones were heating up way beyond the temperature set on the thermostats. I shut off the thermostats but the zones kept getting heat until I finally turned off the boiler. I've...

AC gooes off before reaching desired temp, [ 4 Answers ]

My AC units will shut off before the temp reaches the set temp. I thought is was my thermostat so I replaced it. No change. Example. Temp is reading 80. I set temp for 76. The AC goes on. The thermostat (LuxPro) has a blinking indicater when the unit is blowing. The AC stays on for a few...

A/c shuts off temp never reached [ 5 Answers ]

My heat pump will run cooling mode for only about 30 min. or so. Then the outdoor unit shuts off. The indoor fan keep blowing. The smaller line going into the evaporator freezes between the evaporator and a valve with a capillairy tube that leads to the larger line. Once it thaws which takes about...

Cycling on-off before desired temp is reached [ 2 Answers ]

GMP100-3 gas furnace: The furnace runs for 3-5 minutes then shuts itself off for 2-3 minutes then repeats the start- stop cycle. I turned the thermostat up but it still acts the same. Any tips would be appreciate

New Sauna Heater Trips GFI When Desired Temperature is reached [ 5 Answers ]

I have just installed a new outdoor sauna. The new sauna heater trips the GFI breaker when the thermostat shuts the heater off after reaching the specified temperature. I have a 50 amp GFI breaker in the house 200amp load box. From there I ran #6 wire for 120 feet to an external weather proof...


View more questions Search