Asked Jan 26, 2009, 03:22 PM — 8 Answers
My furnace is buderus with a becket burner, it is about 6 years old and has been serviced every year. I have been having a problem lately with it kicking on when the temp in the house is warmer than the termastate is set at and I know found it has water leaking from it. Can you tell me what might be the problem. It is forced hot water for heating.

8 Answers
21boat's Avatar
21boat Posts: 2,419, Reputation: 1104
Ultra Member
 
#2

Jan 26, 2009, 05:07 PM
The problem is if the boiler is leaking water the automatic fill valve is refilling the boiler jacket and cooling it down. The boiler is set to maintain its temperature in the jacket. When that drops the Becket burner will kick on to get the temp back up I'm the boiler.
This should nit be leaking ANY water its a closed system. Here is the basic possibilities of a leak.
Boiler jackets seals are not sealed in between the jackets.
The cast or steal jacket has a hole in it and is leaking on the floor
The pressure relief valve is going bad and dripping water out of it and on the floor
The seals on the circulator has bad seals.
The hot water lines or the cold water lines is leaking at a joint.
Thats about it.
Any leaking will cause the automatic water feed valve that's on the domestic water line hooked to boiler to open and add COLD water directly to the boiler and then it needs to re fire to bring up heat in the boiler so when you call for heat on the thermostat pre heated hot water is there on demand'
Fix leaks and this should solve the problem. If it doesn't then its another problem but the leak needs fixed first.


Signed 21 Boat

If I Helped To Answer Your Question Please Rate My Answer
Helpful
mikedem7's Avatar
mikedem7 Posts: 104, Reputation: 60
Junior Member
 
#3

Jan 26, 2009, 05:09 PM
You are constantly getting cold water into your furnace which will make it run when the furnace is leaking
Helpful
21boat's Avatar
21boat Posts: 2,419, Reputation: 1104
Ultra Member
 
#4

Jan 26, 2009, 05:30 PM
Just to get our lingo right hear

A Furnace BLOWS air and uses ductwork It has NO water

A Boiler is a hot water system with water that is used to heat the house.

The only way a Furnace leaks water is when The A coil in the plenum condensates while air condition is on
The little drip line
Helpful
Missouri Bound's Avatar
Missouri Bound Posts: 1,300, Reputation: 393
Ultra Member
 
#5

Jan 26, 2009, 05:51 PM
21boat...just to get your lingo straight..."a furnace is a major appliance that is permanentlly installed to provide heat to an interior space through intermediary fluid movement, which may be AIR, STEAM, OR HOT WATER".
Helpful
21boat's Avatar
21boat Posts: 2,419, Reputation: 1104
Ultra Member
 
#6

Jan 26, 2009, 06:52 PM
Quote:
Originally Posted by ;
..."a furnace is a major appliance that is permanently installed to provide heat to an interior space through intermediary fluid movement, which may be AIR, STEAM, OR HOT WATER
Now we are getting to is it an engine or a motor in a car.
An engine/motor is a generic for describing energy and movement. What separates the two is one uses fossil fuel to create the energy. That's why we don't say I need an engine for my power window to work.
When I order a Furnace form one of my supply house its a forced hot air. When I get a quote for a boiler its either water or steam.
We don't call it an Appliance or use the dictionary that way and say Hay I need an appliance to replace your HEAT PLANT So in MY world as an installer ITS a furnace or a BOILER
A Becket burner can go in both. Becket is big in my town as wel as Weil McClain boilers Burhamn boiler are strong here and also MADE here. And I have been installing them for over 20 years now
If you go into the wholesales office at the one of my supply houses and say I need a furnace they will Tell you they don't sell Furnaces only boilers. The other supply house that Does sell furnaces will tell you they don't sell Boilers. So the too vague usage of the word furnace does not apply in my plumbing world Its to generic on definition.
I wasn't trying to bust on anybody hear My repost was to help confirm weather the questioner knew for sure if it was a boiler or a furnace If there is a humidifier in the plenum that could leak water too And again the Beckett Burner goes in both.
If a customer called me to come out and clean there furnace and I showed up without any brushes to clean their Appliance/furnace and I'm standing looking at a boiler with no brushes to clean the jacket in the boiler not to mention the many different size brushes to fit diff boiler jackets. As you see In My world of plumbing and heating we need to define what kind of heat plant it is Ergo furnace boiler
Signed 21 Boat

If I Helped To Answer Your Question Please Rate My Answer
Helpful
hvac1000's Avatar
hvac1000 Posts: 14,539, Reputation: 2381
Heating & Air Conditioning Expert
 
#7

Jan 26, 2009, 07:34 PM


Quote:
Originally Posted by dmd63 View Post
My furnace is buderus with a becket burner, it is about 6 years old and has been serviced every year. I have been having a problem lately with it kicking on when the temp in the house is warmer than the termastate is set at and I know found it has water leaking from it. Can you tell me what might be the problem. It is forced hot water for heating.

Read

http://www.burts.com/warranties/buderus.pdf
Helpful
Missouri Bound's Avatar
Missouri Bound Posts: 1,300, Reputation: 393
Ultra Member
 
#8

Jan 26, 2009, 08:17 PM
21 Boat...I understand where you are coming from and I appreciate it. But the first comment made by DMD was "furnace is Buderus"....they only make hydronic equipment. Many homeowners don't know exactly what makes their heat work, let alone the source of it...With water and air and steam and electric....there is radiant, fan forced, hydronic and I'm sure more designations I've missed. At any rate DMD isn't the expert, you are. If you walk into a customers house and start correcting their "lingo" is that good business? At any rate....
DMD, all of 21boat's suggestions could be your problem.....It's clear he's versed in boiler symptons and repair. I suggest you get a hvac tech who knows boilers to help you. Boilers are great and can last 50 years (had a Weil McClain that did) but they just like all equipment need to be serviced and maintained.
Helpful
21boat's Avatar
21boat Posts: 2,419, Reputation: 1104
Ultra Member
 
#9

Jan 27, 2009, 12:16 AM
Hi Missouri Thank for under standing I wasn't busting Here in My neck of the woods I never heard of Buederus and I didn't bother to look it up for the simple reason that I just needed clarification of it hot air or water. Probably because of the manufacturing of boilers and heat pumps here are strong hear Again Didn't mean to offend. To tell you the truth They Love when I correct the lingo and it makes them feel better knowing the differences and gives them a little more feeling of control having the new knowledge. Today people love that and are in that grove Ergo Big box Stores knowing what's its called especially in plumbing. Many times the clarification of the lingo helps the answerers here especially in the plumbing end etc Thanks for the heads up! On Buederous! Appreciated

Signed 21 Boat

If I Helped To Answer Your Question Please Rate My Answer
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Water leaking from furnace! [ 4 Answers ]

I have a large water pool around the base of my furnace. I unclogged the drain tube leading into the pump..but the water is still coming back. The outside metal covering of the furnace have a lot of condensation on them and sometimes a small layer of ice. The water in the basement looks a...

Water leaking at the top of the furnace [ 3 Answers ]

Just this past fall I had a new furnace installed. I recently just started using the AC and after a couple of days noticed that there is water leaking at the top of the furnace. I have never had any problems with leaking before the new furnace was installed. I have verified that the drain...

Why is my furnace leaking water? [ 2 Answers ]

Why is my furnace leaking water?

Water leaking from gas furnace [ 2 Answers ]

I found water, or liquid leaking from my gas furnace. What can this be? Recently we had a repair man come, he replaced an igniotor. The furnace is 7 years old. HELP!

Gas furnace leaking water [ 3 Answers ]

Discovered water pooling out on to floor and dripping from within furnace--seemingly coming from furnace vent...there is quite a bit of rust that has formed which leads me to think its been going on for a while within the furnace but was not noticed till now after heavy rains, and the pooling...


View more Heating & Air Conditioning questions Search