Bryant 355MAV error 34 & 14 Ignition Lockout
Hi everyone,
I own a Bryant 355MAV furnace which has been installed since Autumn 2001 and run without trouble since then (except a minor airflow issue last winter which was helpfully solved here in this forum).
I've been running the heater for most mornings since early October without issue. However, a couple of days ago, when I turned it on first thing in the morning it never began blowing hot air. After a number of tests here is everything I have been able to learn about the problem --
The unit turns on, but encounters error code 34, Ignition proving Fault, which after a few minutes leads to error 14, Ignition Lockout.
When I turn the unit on from the thermostat, the inducer motor comes on for about 20 seconds or so. Then I can see the hot surface ignitor glow brightly through the burner sight glass on the burner assembly. However, after that NO flame ignites in the burners that I can see.
At this point error 34 is tripped. It tries three more times then shuts down completely, and switches to error 14.
I've inspected the furnace according to the instructions on the inside panel for the 34 error. All the components inside the burner assembly, including the ignitor and the flame sensor, are clean and mostly free of oxidization as far as I can tell.
I could smell a faint whiff of natural gas on at least one of the tests during the point where the furnace tries to turn on the gas burners. I have to emphasize that it was very faint, like from a gas stove which takes a second or two to fire. There is NO gas fumes at any other time, such as when the unit is not functioning. The manual gas shut-off valve was on, and the gas lines leading up to and inside the unit all seem unmoved and undamaged.
The green ground wire to the sheet metal is still affixed.
The vent and combustion-air pipes all seem fine, and the vent on my roof is free of obstruction as far as I can tell.
I haven't any work done on natural gas lines to my house (or in the neighborhood), and my other gas appliances have not had any trouble that I know of.
If anyone has any advice or tips about how to determine what the likely problem is, I'd really appreciate it! If I've neglected to mention anything, please ask! Thanks in advance!
If it's helpful, here's the complete text from the inside panel for error 34:
Code:
Ignition proving fault.
Control will try three more times before a lockout 14 occurs.
Check for gas valve defective or gas valve turned off
Defective hot surface ignitor
Low inlet gas pressure
Manual valve shut-off
Flame sensor must be ungrounded
Green wire MUST be connected to furnace sheet metal
Proper flame sense micro-amps
Inadequate flame carry-over or rough ignition
Control ground continuity
Oxide build-up on flame sensor (clean with fine steel wool)