  • Oct 9, 2011, 12:12 PM
    Gjazzworks
    Bryant 310 furnace flashing LED error code.
    My Bryant 310 furnace is flashing error code. 3 quick flashes, 3 long flashes. What does this mean?
  • Oct 9, 2011, 07:01 PM
    T-Top
    LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent
    Switch (if used) is open. Blower will run for 4 minutes or until open switch remakes
    Whichever is longer. If open longer than 3 minutes, code changes to lockout #13.
    If open less than 3 minutes status code #33 continues to flash until blower shuts off.
    Flame rollout switch and BVSS require manual reset. Check for: - Restricted vent
    - Proper vent sizing - Loose blower wheel. - Excessive wind
    - Dirty filter or restricted duct system.
    - Defective blower motor or capacitor. - Defective switch or connections.