Home > Home & Garden > Heating & Air Conditioning   »   Blower won't run in auto for heat with oil furnace

 
Thread Tools Search this Thread Display Modes
Question
 
 
#1  
Old Oct 30, 2007, 03:09 PM
blueskies4ever
New Member
blueskies4ever is offline
 
Join Date: Oct 2007
Posts: 5
blueskies4ever See this member's comment history on his/her Profile page.
Blower won't run in auto for heat with oil furnace

I have an oil furnace.

A/C works fine.

Heat last season worked fine.

Started up furnace this year just fine. But blower would not start on auto. The blower will run in heat mode when set to On.

I replaced the Limit Switch in the Plenum. No change.

I replaced the Fan Relay. No change.

Not sure what to do next.

Any ideas?

Thanks in advance

Reply With Quote
 
     

Answers
 
 
Old Oct 30, 2007, 04:50 PM   #2  
Junior Member
J Costa is offline
 
Join Date: Aug 2007
Posts: 89
J Costa See this member's comment history on his/her Profile page.
did you check your thermastat?
  Reply With Quote
 
     
 
 
Old Oct 30, 2007, 05:19 PM   #3  
Junior Member
eschuen is offline
 
Join Date: Oct 2007
Posts: 62
eschuen See this member's comment history on his/her Profile page.
you might check the wiring going to the fan motor if this is a 2 speed motor. Sounds like the low speed portion of the motor might have a problem. Check voltage at relay and go from there
  Reply With Quote
 
     
 
 
Old Oct 30, 2007, 05:24 PM   #4  
New Member
blueskies4ever is offline
 
Join Date: Oct 2007
Posts: 5
blueskies4ever See this member's comment history on his/her Profile page.
Quote:
Originally Posted by eschuen
you might check the wiring going to the fan motor if this is a 2 speed motor. Sounds like the low speed portion of the motor might have a problem. Check voltage at relay and go from there
If there was an issue with the wiring to the fan motor, wouldn't this also be a problem in the A/C mode? In any event, unless I'm misunderstanding you, I only have one speed other than off.

Thanks.
  Reply With Quote
 
     
 
 
Old Oct 30, 2007, 07:57 PM   #5  
Über Member
labman is offline
 
Join Date: Feb 2003
Location: Northern US
Posts: 10,646
labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.
In most systems the blower uses a slower speed from a different winding controled by a different relay than in A/C or fan on. So it is perfectly possible for the blower to work fine in A/C andfan on, but not heat. Look at the wires to the blwer motor. a single speed motor would only have a hot and a neutral. It is has more than 2 wires, it is a multiple speed motor.

Note, in heat, the thermostat has nothing to do with the blower. The blower is controlled by a limit switch or a timer on the control board.
  Reply With Quote
 
     
 
 
Old Oct 31, 2007, 06:14 PM   #6  
New Member
blueskies4ever is offline
 
Join Date: Oct 2007
Posts: 5
blueskies4ever See this member's comment history on his/her Profile page.
Quote:
Originally Posted by labman
In most systems the blower uses a slower speed from a different winding controled by a different relay than in A/C or fan on. So it is perfectly possible for the blower to work fine in A/C andfan on, but not heat. Look at the wires to the blwer motor. a single speed motor would only have a hot and a neutral. It is has more than 2 wires, it is a multiple speed motor.

Note, in heat, the thermostat has nothing to do with the blower. The blower is controlled by a limit switch or a timer on the control board.
Thanks for the feedback.

There are only two wires going to the motor. The motor has several wires that give you the option of what speed to run at depending on which one is connected. The red wire on the motor is the one that is connected and sets the speed at low.

Also, my furnace is of a vintage that does not use a control board. Other than the limit switch in the plenum (replaced), the fan relay (replaced), there is one additional switching component. It has 3 low voltage wires that run back to the relay and has one hot wire. There is a "dial" on the switch that sets a time adjustment between 150 and 200 sec. I assume it is to set the length of time the blower runs after the furnace switches off.

Thanks again.
  Reply With Quote
 
     
 
 
Old Nov 3, 2007, 06:04 AM   #7  
New Member
blueskies4ever is offline
 
Join Date: Oct 2007
Posts: 5
blueskies4ever See this member's comment history on his/her Profile page.
Quote:
Originally Posted by blueskies4ever
Thanks for the feedback.

There are only two wires going to the motor. The motor has several wires that give you the option of what speed to run at depending on which one is connected. The red wire on the motor is the one that is connected and sets the speed at low.

Also, my furnace is of a vintage that does not use a control board. Other than the limit switch in the plenum (replaced), the fan relay (replaced), there is one additional switching component. It has 3 low voltage wires that run back to the relay and has one hot wire. There is a "dial" on the switch that sets a time adjustment between 150 and 200 sec. I assume it is to set the length of time the blower runs after the furnace switches off.

Thanks again.
I'm still having the same issue as originally described and as per my follow up. I thought I'd try and put this out there one last time in the hope that someone might have an idea of what my problem might be.

Thanks.
  Reply With Quote
 
     
 
 
Old Nov 3, 2007, 12:51 PM   #8  
Über Member
labman is offline
 
Join Date: Feb 2003
Location: Northern US
Posts: 10,646
labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.
I frequently leave questions hoping somebody that knows more than me answers. Often as not, it is somebody that knows less.

Try jumping the hot wire to the timing switch to the terminal on the relay that the other wire goes to. If the motor then runs, the switch is bad. Remove it and take it to a HVAC supply and let them match it.
  Reply With Quote
 
     
 
 
Old Nov 3, 2007, 05:21 PM   #9  
New Member
blueskies4ever is offline
 
Join Date: Oct 2007
Posts: 5
blueskies4ever See this member's comment history on his/her Profile page.
Quote:
Originally Posted by labman
I frequently leave questions hoping somebody that knows more than me answers. Often as not, it is somebody that knows less.

Try jumping the hot wire to the timing switch to the terminal on the relay that the other wire goes to. If the motor then runs, the switch is bad. Remove it and take it to a HVAC supply and let them match it.
I'm afraid I must be dense. There is one hot wire going to the timing switch. When you are saying to jump this to the terminal on the relay that the other wire goes to, I'm afraid I don't understand how are you distinguishing the other wire. I also assume the switch you are suggesting I fault isolate is the one with the time dial on it, is that right?

Thanks again.
  Reply With Quote
 
     
 
 
Old Dec 22, 2007, 10:21 AM   #10  
New Member
homefix is offline
 
Join Date: Dec 2007
Posts: 1
homefix See this member's comment history on his/her Profile page.
Say blueskies4ever, how did you fix this relay problem? I have a very simlar problem.
  Reply With Quote
 
     

Your Answer
Email me when someone replies to my answer
Join Login





Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

 
Similar Sponsors


Thread Tools
Show Printable Version Show Printable Version
Email this Page Email this Page

Similar Threads
Furnace blower not working in Auto Mode
(0 replies)
Programmable Thermostat, Fan runs, Heat/Air do not run in Auto setting
(10 replies)
Furnace blower can not auto start
(23 replies)
run blower without heat??
(2 replies)
Furnace won't heat in Auto
(2 replies)