    Blower runs on "ON", but not on "Auto"
    Hello All,
    I have a Goodman COMBINATION HEATING AND COOLING OUTDOOR UNITS PG/PGX SERIES (100K BTU). It failed to warm the space. The fan would not run on “ON” or “Auto” mode. Upon investigating, there is no power to the unit due to 25 amps fuses blown. Replaced with new fuses. Power was supplied to the unit, fan can turn on manually (“ON” mode).
    When the thermostat was in Heat and Auto mode, the temperature set at 80F. The furnace ignited, felt a breeze of warm air for 3-4 minutes, but the blower was not kicked in to deliver the heat. After 3-4 minutes, the furnace shut down. Reset the thermostat (heat OFF), set Heat and Auto. This time, it was NO HEAT and NO FAN

    According to manual:
    SEQUENCE OF OPERATION
    1. Thermostat calls for heat.
    2. Combustion motor is energized, combustion motor interlock is made.
    3. Ignition spark is energized.
    4. Pilot valve opens and pilot burner lights
    5. Sensor proves pilot flame.
    6. Ignition spark de-energized.
    7. The main gas valve is energized.
    8. Pilot flame lights the main burners.
    9. Thermostat is satisfied and opens. The main and pilot valves are de-energized, shutting down main and pilot flames.

    Here is the wiring instruction:
    LEAD -> THERMOSTAT
    White -> W (Heat)
    Green -> G (Fan)
    Yellow -> Y (Cool)
    Red R -> (24V.)
    Orange -> Y1 Only when economizer is utilized
    Pink -> Y2" (not available)

    Can anyone please help to troubleshoot this problem? Any inputs are greatly appreciated.
    Thanks, Seminole
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Jan 17, 2007, 05:02 PM
    Sounds like the circuit board is bad, since the fan relay on the board has failed, the blower never turns on, the furnace overheats and the main limit turns everything off when it realizes the furnace is overheated.
    seminole's Avatar
    seminole Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 18, 2007, 08:00 AM
    Quote Originally Posted by seminole
    Hello All,
    I have a Goodman COMBINATION HEATING AND COOLING OUTDOOR UNITS PG/PGX SERIES (100K BTU). It failed to warm the space. The fan would not run on “ON” or “Auto” mode. Upon investigating, there is no power to the unit due to 25 amps fuses blown. Replaced with new fuses. Power was supplied to the unit, fan can turn on manually (“ON” mode).
    When the thermostat was in Heat and Auto mode, the temperature set at 80F. The furnace ignited, felt a breeze of warm air for 3-4 minutes, but the blower was not kicked in to deliver the heat. After 3-4 minutes, the furnace shut down. Reset the thermostat (heat OFF), set Heat and Auto. This time, it was NO HEAT and NO FAN

    According to manual:
    SEQUENCE OF OPERATION
    1. Thermostat calls for heat.
    2. Combustion motor is energized, combustion motor interlock is made.
    3. Ignition spark is energized.
    4. Pilot valve opens and pilot burner lights
    5. Sensor proves pilot flame.
    6. Ignition spark de-energized.
    7. The main gas valve is energized.
    8. Pilot flame lights the main burners.
    9. Thermostat is satisfied and opens. The main and pilot valves are de-energized, shutting down main and pilot flames.

    Here is the wiring instruction:
    LEAD -> THERMOSTAT
    White -> W (Heat)
    Green -> G (Fan)
    Yellow -> Y (Cool)
    Red R -> (24V.)
    Orange -> Y1 Only when economizer is utilized
    Pink -> Y2" (not available)

    Can anyone please help to troubleshoot this problem? Any inputs are greatly appreciated.
    Thanks, Seminole
    Many thanks to NorthernHeat and Labman. How can I verify the relay is bad? Where do I find a replacement board?
    Thanks, Seminole.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #4

    Jan 18, 2007, 03:31 PM
    When blower is supposed to turn on you don't get 120 volts to the appropriate female stab pin on the board. Good luck finding a board on your own, wholesalers only sell to licensed contractors.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Fan Blower not working in "ON" or "AUTO" in heat or AC [ 13 Answers ]

Got home from the Brewer game this afternoon and noticed the house was warm(78). Outside was 91. I checked the T-stat and it was set correct. Noticed the air vents weren't blowing anything. Went outside and the condenser and fan was running fine. Then I went downstairs to the furnace unit to see...

Pink pill with "watson" and "502" on it [ 2 Answers ]

What kind of pill is pink and has watson 502 on it?

Heater blows cold when "On", not at all on "Auto" [ 1 Answers ]

Our gas heater is 7 years old, and has worked fine in the two years we've rented here. This winter though, we can't get it to work consistently. When on "Auto", it doesn't turn on at all, no matter what temperature we select, and when we turn the fan to "On", it simply blows cold air. It...

The blower doesn't start on "Auto" [ 10 Answers ]

Please someone help me. My furnace Lennox G20Q3/4E-100-5 behaves as follows: 1) Fan is on "Auto" 2) Thermostat calls for heat 3) Green light comes "On" on IPI module and then burner comes "On" 4) Flame occurs 5) Blower doesn't come "On". After a while, the burner stops due to safety. It...


View more questions Search