    Blower not working and blower running all the time
    I have a Lennox electric furnace that's about 10 years old or so, the elements come on but no blower. There is a summer fan switch that will make the blower run when switched on, but it will not come on with a call for heat. Also at my work, there is a york gas pack that is probably 15 years old. The blower runs all the time even if I disconnect the wire from the t- stat and the gas pack. Any suggestions on either problem?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 2, 2008, 09:44 PM
    On the Lennox I would check for a defective blower relay or the blower might be controlled by a heat sequencer.

    On the gas pack you need to check the blower relay circuit. I would start by disconnecting the thermostat wires at the unit. This is done to check for shorts in the wire itself. If the blower still runs then it is in the unit itself.
    Wdbutcher's Avatar
    Wdbutcher Posts: 3, Reputation: 1
    New Member
     
    #3

    Nov 3, 2008, 12:00 PM

    I have a trane that the blower for the chimney keeps running , even after the call for heat any ideas?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Blower keep running [ 1 Answers ]

I don't why my blower keeps on running after turning off the unit

Blower keep running [ 1 Answers ]

I don't know why my blower keeps on running after turning off the unit

Running blower at slow speed all the time, and high when compressor runs. [ 1 Answers ]

I have a Carrier 58PAV090 furnace air handler. The fan has multiple leads which are used to run the blower at different speeds. The black is for High speed, yellow for medium high, blue for medium low and red for low. In the cooling mode, the blower turns on when the thermostat calls for cooling...

Heat and Air not working on Attic unit, but blower working. [ 1 Answers ]

The blower is working fine on our Heating and Air Conditioning unit but neither the Air or Heat will work. The emergency Heat works fine though. The unit is a Carrier with the words American Standard written on the outside fan unit. What should I look for before calling a tech or what would this be...

Blower continuosly running [ 1 Answers ]

Trying to figure out why fan keeps blowing inside house and outside heat pump not running. Replaced thermostat and that did not fix problem. Its blowing heat though but it runs continuously and the light bill is outrageous. Was thinking of replacing fuses outside or could it be adjust a limit...


View more questions Search