    Blower Fan on gas Comfortmaker RPG Heat Exchanger runs intermittently
    Hello,
    I'm new here, and I've been reading a lot (well, 4 or 5 pages anyway) of what's already been asked, and I haven't found my specific problem... yet.

    This gas hot air furnace was installed circa 1987?
    So,
    Here's what's happening. (I actually timed these cycles with a second-hand.)
    Turn up thermostat; furnace kicks in & burners start cranking.
    Blower fan is triggered & runs for 44 seconds, then shuts off.
    Burners continue operating for 1 minute, 41 seconds.
    Blower fan is triggered & runs for 45 seconds, then shuts off.
    Burners continue operating for 1 minute, 40 seconds.
    Blower fan is triggered & runs for 45 seconds, then shuts off.
    Burners continue operating for 1 minute, 38 seconds.
    Blower fan is triggered & runs for 45 seconds, then shuts off.
    Burners continue operating for 1 minute, 40 seconds.
    Blower fan is triggered & runs for 45 seconds, then shuts off.
    Burners continue operating for 1 minute, 49 seconds.

    This process continues until the thermostat reaches the agreed-upon temperature. It is a Honeywell thermostat, probably rather vintage and I can see the model (?) numbers:
    T87F2360 3 8443. It's currently on a setting of "4" in the little brass triangle.

    Do you think this is a thermostat problem a fan switch problem or other? :confused:
    If it's something I'll need a professional to look at, any guesstimates as to probable cost?

    Any advice very much appreciated. I really hadn't budgeted on a furnace problem right now, you know? :(

    Thanks so much,

    Diane
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 19, 2008, 01:17 PM
    Do you think this is a thermostat problem a fan switch problem

    It could be either one.

    Did this just start happening?

    Have you lived there long enough to know if this is a new problem?

    If it is a new problem it could be the fan switch on the furnace. Usually the thermostat will not change its anticipation settings since these settings have to be changed manually.

    Have you changed the thermostat?
    dplantlady's Avatar
    dplantlady Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 19, 2008, 01:58 PM

    Hmmm... either one, eh?
    But I got in the general ball park, though. I've impressed myself.

    As I recall, (I own the house but hadn't lived here for a year & a half... silly me, I thought I'd get renovation work done if I lived somewhere else... HAH!), it had started to happen at the end of the last heating season when I was living here. And since I just turned the heat on for the first time today, it's all coming back.

    I don't believe I've changed the thermostat, only to turn it down or up. Haven't fiddled with anything under the cover.

    Thanks for taking the time to try to help figure this out.

    Diane
    deb3131's Avatar
    deb3131 Posts: 2, Reputation: 1
    New Member
     
    #4

    Jan 24, 2011, 10:15 AM
    Its your limited switch

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Bryant Plus 90 blower runs intermittently [ 7 Answers ]

I have a Bryant 90 Plus (350 MAV) gas furnace that is about 13 years old with an intermittent problem. The inducer motor starts, igniter lights, gas valve opens, and burner lights and runs but occasionally the blower motor will not start. When this occurs the plenum attached to the furnace gets...

Heat Pump runs, blower does not [ 3 Answers ]

My Furnace/Heat Pump seems to be working incorrectly. There are times when the Heat Pump outside will run continuously while the thermostat says "heating" however, the blower doesn't come on inside. The coil coming into my furnace unit gets very hot. I have to turn off the unit completely for...

Blower runs on auto & on for AC, but only on for heat [ 1 Answers ]

I had my blower replaced this summer & it runs well for the AC... when I turned the heat on it only works when it is in the on position, not auto... the themostat I have is programable:(

Oil furnace Blower runs no heat [ 9 Answers ]

I am having a intermintant problem with my furnace, I came home the blower was on no heat , I checked the themostat setting - ficked the service switch off and on a couple of times- burner started, I can hear the burner when it comes on, the furnace ran all day without problem I wake in the night...

No heat, blower runs constantly, carrier gas furnace [ 7 Answers ]

This am we I got up the blower on my carrier series 100 gas furnace (approx 10 years old)was running and blowing out cold air. Even with the thermostat turned to off the blower runs constantly. The only way to stop the blower from running is to turn the switch on the side of the furnace to off or...