    Aux Heat stays on beyond the T-Stat Setting
    This is a rather interesting problem. I've got a heat pump with a single stage Auxiliary/Emergency heat, and until this fall there hadn't been a problem with it.

    The symptom is rather straightforward: during the day, you'll be around the house and start to think that boy, it's rather warm around here and that the fan has been running a lot. You go to check the thermostat to find that the temp is 75F in the house when the temp is set to 70F. Turning the T-stat to OFF and AUTO does nothing, and if you go outside to check the heat pump it's actually not running, indicating that the Auxiliary Heat is running. If you powercycle the system, you can get the system to behave for a while.

    We've had the sequencer changed, and then when the symptoms returned the HVAC guy investigated and found the t-stat calling for Aux Heat. The t-stat was then replaced. Now, a week later, the symptoms are back AGAIN. I'd bet money that if I took a voltmeter and checked, the t-stat will once again say it's calling for heat, but the odds that I've two bad t-stats in a row is probably remote. Am I potentially looking at something like a bad wire between the t-stat and the unit, or is there something else that I'm not considering?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 23, 2008, 03:47 AM
    At this point it is a guessing game. It could be a shorted low voltage line from the unit to the thermostat. The short could be right behind the thermostat or in the wall.

    Something in the control chain is causing the heat to stay on. I do not believe two thermostats would be defective but you never know. It could be the thermostat is wired incorrectly to start with.
    flyerfan1991's Avatar
    flyerfan1991 Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 25, 2008, 07:37 PM
    Quote Originally Posted by hvac1000 View Post
    At this point it is a guessing game. It could be a shorted low voltage line from the unit to the thermostat. The short could be right behind the thermostat or in the wall.

    Something in the control chain is causing the heat to stay on. I do not believe two thermostats would be defective but you never know. It could be the thermostat is wired incorrectly to start with.
    Since I posted I haven't seen the issue since, but I'm keeping close tabs on the unit.

    Thanks for the idea; if I see the issue again I might want to consider running some new wire from the unit to the t-stat and see if that fixes things.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Nov 25, 2008, 10:47 PM
    Replacing the wire might be a good idea but you can sound the wire out with a ohm meter to prevent the expense.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wrong t-stat setting [ 7 Answers ]

Would there be any system performance issues if the T-stat settings were incorrectly set to 3 stage heat / 2 stage cool instead of 2 stage heat / 1 stage cool? I'm running a Trane XL14i heat pump with a variable speed handler. The T-stat is a TCONT802A. Thank you in advance for any replys.

Heat stays on [ 2 Answers ]

Hello. Our heating unit (inside unit) will not shut off once the desired temperature is met in the house. It isn't the thermostat because it says it's shutting off, but it really doesn't. We've had someone at our house today to look at it, and they say the computer board is fried. Does that...

Furnace Blower stays on, no heat [ 2 Answers ]

Hello, I have an older Bryant furnace model # 396gadd36075. I turned on the heat the other day and the no heat. I notice the unit had been turned off (pilot was not lit), apparently by the service company I use when they came to do the spring check for the AC. I followed the instructions to...

Wiring T-stat to control heat lamp [ 14 Answers ]

I would like to heat an area (128cf with no moving air) using a 1500W heat lamp(s). I would also like to control the temp. inside this space with a standard home T-stat. mounted inside the area being heated. I understand the T-stat uses 24v while the heat source is 120v. I would also like to add a...

Replaced T-stat batteries... Now the AC/HEAT does not work at all! [ 5 Answers ]

Good morning and Happy Columbus Day everyone. I must say that anyone's help and feedback will be much appreciated. Last night the Thermostat (Honeywell Programmable CT8602) gave the low battery light as my wife was looking to drop it a degree before bed so she decided to replace the batteries. ...


View more questions Search