    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #1

    May 6, 2009, 07:31 AM
    Amana Heat pump High pressure switch tripping
    Called tech found unit pressure switch tripped, reset added freon. Lasted less than a week. Appears tripped again. He mentioned fan could be the culprit when he was out.

    Is there a way to eliminate this as a cause? Any other possible solutions? Brand new filter in unit after first episode.
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #2

    May 6, 2009, 01:25 PM

    Too much freon, line restriction, fan going bad. Reversing valve stuck, there are a number of things that could be causing this.
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #3

    May 6, 2009, 06:47 PM
    Quote Originally Posted by Joshdta View Post
    too much freon, line restriction, fan going bad. Reversing valve stuck, there are a number of things that could be causing this.
    Any way to rule any of this out?
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #4

    May 6, 2009, 07:23 PM

    Have you ever hurd the unit running and the fan was not spinning? Does it trip in heat or cool?
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #5

    May 7, 2009, 06:00 AM
    Quote Originally Posted by Joshdta View Post
    Have you ever hurd the unit running and the fan was not spinning? Does it trip in heat or cool?
    This is tripped in cooling. I turn unit on cool and go outside and you can hear something trying to engage. I am almost sure the high pressure reset is tripped. When tech was out he turned the unit on cooling also and there was no response from the outside unit until he opened the access panel and tripped the reset. Fan started up at that point and it cooled house the rest of that day. Went to use a day or two later and the wife said she thought it wasn't cooling again.

    I did as he had done when he visited and the outdoor fan is not moving again. I have yet to try the reset though.
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #6

    May 7, 2009, 01:27 PM

    How old is the unit? Maybe it is dirty. Spray it off good with a water hose this will bring the pressures donw and hopfully keep it from triping again.
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #7

    May 7, 2009, 06:56 PM
    Quote Originally Posted by Joshdta View Post
    how old is the unit? maybe it is dirty. spray it off good with a water hose this will bring the pressures donw and hopfully keep it from triping again.
    6-7 years. You talking spraying water and rinsing the fins out on outdoor unit? They are clean.
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #8

    May 7, 2009, 06:58 PM

    So you have clean fins? The freon charge is right? Clean filter inside? Could be a line dryer is cloged.
    aj5150's Avatar
    aj5150 Posts: 9, Reputation: 1
    New Member
     
    #9

    May 7, 2009, 07:07 PM

    Did you say the high pressure switch is kicking or the breaker
    If the high pressure switch depending on the unit the switch could be bad
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #10

    May 7, 2009, 07:11 PM
    Let me guess do you have a rheem heat pump? You can have a bad Txv on the heat pump or fancoil. If they add freon in the summer time and it trips out in the winter(bad txv at the evaporator coil). If they add freon in the winter months and it trips in the summer(bad txv at the heat pump,check valve, restricted screen before the check valve)
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #11

    May 8, 2009, 05:24 AM
    So everyone has clear info here this is an Amana Heat pump. The charge should be right since the tech was here last week and he added 1 lb if I remember correctly.

    He claims that if the High Pressure Switch keeps kicking out the fan motor on the outside unit may be going bad.

    Just don't want to pay for a part and it not be the root cause.
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #12

    May 8, 2009, 05:27 AM

    If the fan motor was going bad, if you watch the unit it should stop running with in 15 minutes or so. This will tell you weither or not it is the fan. But I bet there is anouther problem.
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #13

    May 10, 2009, 01:20 PM
    Quote Originally Posted by Joshdta View Post
    If the fan motor was going bad, if you watch the unit it sould stop running with in 15 mins or so. this will tell you weither or not it is the fan. but i bet there is anouther problem.
    I just tried to reset the high pressure switch to see if the fan would come back on to test this out. I pushed the reset switch in but the fan did not respond?
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #14

    May 10, 2009, 04:09 PM

    Might need a capasitor or a n ew fan motor.



    http://img.diytrade.com/cdimg/377701..._Capacitor.jpg
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #15

    May 10, 2009, 06:12 PM
    Quote Originally Posted by Joshdta View Post
    might need a capasitor or a n ew fan motor.



    http://img.diytrade.com/cdimg/377701..._Capacitor.jpg
    Is there a way to test either of these?
    Joshdta's Avatar
    Joshdta Posts: 2,549, Reputation: 45
    Ultra Member
     
    #16

    May 10, 2009, 06:17 PM

    Check to see if the top of the capasitor is swollen or if a wire is burnt
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #17

    May 10, 2009, 08:20 PM
    I would call the people back out, they should stand behind their work. The question is if the high pressure switch was tripped why did he add freon? Low on freon = low pressure not high pressure if you add refrigerant it only makes the pressures higher.
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #18

    May 11, 2009, 05:23 AM
    Tech coming back out today. Hopefully we get this resolved.
    pvbearcat234's Avatar
    pvbearcat234 Posts: 9, Reputation: 1
    New Member
     
    #19

    Jun 10, 2009, 06:08 AM
    Quote Originally Posted by pvbearcat234 View Post
    Tech coming back out today. Hopefully we get this resolved.
    Well the story saga continues. Upon coming back out he did find a bad capacitor. Ran for a day or two and down again. Checked switch did not appear tripped. Called tech again now out of freon. Since I tried to reset this may be my mistake$$$$$

    Leaking at pressure switch reset base. He repaired and recharged system, OUCH, lasted 2 days maybe. I wasn't about to touch this thing and check that reset again. Upon his return trip the switch was tripped again.

    He suspects the fan or the switch itself. I monitored the unit every half hour for the next 3 hours and unit did not trip out. Motor on fan not hot. Unit is now running for the second day in a row.

    He mentioned jumpering the other pressure swich and installing an external one?

    Are we headed in the right direction here or are we chasing our tails. Seems I am back to square 1 with a definite hole in the wallet.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #20

    Jun 11, 2009, 07:38 PM
    Its hard to find some problems when it faults out after the tech is gone and working fine while their. A weak pressure switch is what I would start to look at and to rule it out is to only bypass the old and install the new. If the switch is soldered in place add an external switch to the liquid line for temp use. It's a start. Your problem is not uncommon sometimes it takes the prosses of elimination to find the problem.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Rheem high pressure switch keeps tripping [ 10 Answers ]

Not sure if I've summarized the issue exactly right, but my downstairs, outside unit keeps switching off the past several days. I will feel air coming out of my registers but it isn't very warm. I have to go outside several times a day to push the red button to fire up the outside unit. Once I do...

How much freon should be in my amana heat pump, I think it is 2 ton [ 2 Answers ]

How much freon shoud be in my amana heat pump, I think it is 2 ton

Need pressure switch for Amana [ 5 Answers ]

The pressure switch on my 3.5 ton Amana heat pump needs replacing. My local professional checked on part availability after leaving yesterday, and called me back indicating the cost for the switch alone would be approx. $975.00. Hoping to do better than THAT! At any rate, the many many pressure...

Amana 80 sseII, Pressure Switch stuck open! [ 1 Answers ]

Hi, I have a Amana 80 SSE II furnace 5 years old which is giving me an error of pressure switch stuck open. (red light flashes three times). Any ideas as to trouble shooting the problem. The vacuum tube to switch is clear. Can I test the switch to know if it is working correctly. Any other ideas...

Heat Pumo high pressure switch [ 1 Answers ]

Heat will work fine through a cycle but after it completes cycle it goes off on the high pressure switch. It is a Ruud. The indoor filter is clean and coils on condensing unit are clean. I have to reset condensing unit and it will run fine through that cyle then repeats problem. Any ideas as to...


View more questions Search