| is it just the outside unit that continues to run, or does the indoor blower run too? What breaker are you turning off, the furnace breaker or the condenser breaker. furnace breaker will be 120, condenser unit will be 240.
If only outside condenser unit is running, it sounds like you have a stuck contactor in outside unit. |