    AC freezing up.
    Installed it all and charged it on Sunday. Coil is 2" above furnace, called a guy to braze pipes and check pressure. Said all was fine and good. Air was good and cold but it was clear some ductwork needed to be done so I am planning that, but I got plenty of return air and now I also got an inch of ice on my big copper line. Could duct restrictions on the output side of the system cause this much freezing? I still got a hot small line so I assume the freon is good, but I guess there is no way to tell without calling the service guy back out? Any input is appriciated.

    PS, 4 ton 12 seer goodman split system with matched components.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Aug 31, 2005, 03:26 PM
    I would recheck the pressures and if they are OK, perhaps speed up the fan or reduce the restriction in the duct work if you can.
    Socrates's Avatar
    Socrates Posts: 9, Reputation: 1
    New Member
     
    #3

    Sep 1, 2005, 04:30 PM
    Found one MAJOR problem, but no real solution short of a new furnace. It has a 3 ton blower in the furnace (Brand new 2005 Goodman) but my new system is 4 ton, oops. I was thinking of a new blower motor with like twice the rpms, but how well will this work? Any other options besides a new furnace?

    Anyone know how much CFM airflow over the coil I need for 4 tons?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Sep 1, 2005, 05:14 PM
    Most of the newer blowers have several speeds available, depending on which windings are connected. If you have the installation manual for the furnace, figure out how to use the highest speed, and see how it does. There may be a limit to the speeds available. There may or may not be room for a physically larger blower. Perhaps you could even add an auxiliary one in a duct. Most control are set up to use a faster blower speed for A/C than heating. Sorry I don't know more details.
    Socrates's Avatar
    Socrates Posts: 9, Reputation: 1
    New Member
     
    #5

    Sep 1, 2005, 07:29 PM
    So far I gathered it is about 400cfm per ton. As for aux blower, that is what I was thinking, I got a huge blower from an evap cooler, I was going to try it out, it moves about 4000 cfm so it may work OK.
    omar64's Avatar
    omar64 Posts: 1, Reputation: 1
    New Member
     
    #6

    Mar 4, 2007, 02:39 PM
    Quote Originally Posted by Socrates
    Installed it all and charged it on Sunday. Coil is 2" above furnace, called a guy to braze pipes and check pressure. Said all was fine and good. Air was good and cold but it was clear some ductwork needed to be done so I am planning that, but I got plenty of return air and now I also got an inch of ice on my big copper line. Could duct restrictions on the output side of the system cause this much freezing? I still got a hot small line so I assume the freon is good, but I guess there is no way to tell without calling the service guy back out? Any input is appriciated.

    PS, 4 ton 12 seer goodman split system with matched components.
    You need more freon

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

I'm Freezing! [ 6 Answers ]

It seems pretty much normal that most women are colder than men, but this is just bad. I am constantly shivering in my own house, while my husband is sweating. I wear sweat shirts and pants ALL the time! My teeth chatter at work... and I wear a jacket in the office! I have been told I need more...

Intermittent freezing up [ 3 Answers ]

Hello, Hope you can help. Recently I've had a problem with intermittent freeze up of the evap coil of my downstairs central AC. Multiple technicians have been here with no resolution of the problem. I did have to have the evap coil replaced earlier this week due to a leak in the drain pan - and it...

My PC is always freezing & rebooting [ 8 Answers ]

I have Windows XP. Every time I try to play free bingo the computer just freezes or reboots after a short time. I get an error message that says Error Signature BC Code 100000dl BCP1:0000F4F9 BCP200000002 BCP300000000 BCP4:F7FBB838 OSVER:5-1-2600 sp:2-0 pRODUCT:256-1 Please can you help. The PC...

Freezing problems [ 3 Answers ]

My computer freezes up all the time.. especially if I set to long at any site.I run norton protection for virus and spy ware, also use adaware se pesonal and clean my regestry on a daily basis--any ideas? Is there a way to reset my computer and wipe out all files? Thank you:confused:

Freezing [ 1 Answers ]

Hi, My computer freezes when I am trying to watch Internet TV or stream video. Does anybody knows what is the problem? Tx


View more questions Search