    TxGreaseMonkey's Avatar
    TxGreaseMonkey Posts: 16,761, Reputation: 5597
    Uber Member
     
    #1

    Jul 11, 2007, 08:10 PM
    AC Condenser Unit Delay on Break (DOB) Timers
    Turn thermostat OFF, pull AC disconnect to condenser unit, and turn off furnace breaker (power to contactor coil) before performing any work. Use non-contact voltage meter to verify power is off. Finally, use a large plastic handle screwdriver between contactor and ground to confirm power is off.

    Then, install a Delay on Break (DOB) Timer to your home air conditioner's condenser unit, if it didn't come with one (most don't). Anti-short cycle timers protect compressor and contactor from high Locked Rotor Amperage (LRA) damage, when lightning or other power outages cause power to slam off and then back on. Popular products include ICM 203B, which is adjustable from 2 seconds to 10 minutes. 5 minutes is usually sufficient to allow internal compressor pressures to equalize. Remove wire from contactor coil and attach to Terminal 3 (Input) on DOB Timer. Connect jumper wire from DOB Timer Terminal 1 (Load) to contactor coil. This is cheap insurance to protect a major investment.
    acetc's Avatar
    acetc Posts: 1,004, Reputation: 79
    Ultra Member
     
    #2

    Jul 11, 2007, 09:05 PM
    You may be on the right track BUT I think you meant a time delay relay to delay on make, not break and nix the scerw driver trick, use a volt meter.
    hvacservicetech_07's Avatar
    hvacservicetech_07 Posts: 1,083, Reputation: 75
    Ultra Member
     
    #3

    Jul 11, 2007, 09:27 PM
    Most newer digital thermostats have built in time delays.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Jul 11, 2007, 10:26 PM
    ((use a large plastic handle screwdriver between contactor and ground to confirm power is off.)) When the tip of the screw driver blows up in your face you might get burns and loose an eye. Not a good idea. Timers have been around for over 30 years with Carrier using a electro mechanical one. They work great. I guess if you really want to save your A/C and make it last longer a hard start kit would be in order.
    TxGreaseMonkey's Avatar
    TxGreaseMonkey Posts: 16,761, Reputation: 5597
    Uber Member
     
    #5

    Jul 12, 2007, 07:10 AM
    Yes, most digital thermostats provide a 4-minute delay after shutting off the compressor before it can be restarted. This feature prevents damage to the compressor caused by rapid cycling. However, most do not provide a delay when there are power outages--this is the key point.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Jul 12, 2007, 07:40 AM
    Quote Originally Posted by txgreasemonkey
    Yes, most digital thermostats provide a 4-minute delay after shutting off the compressor before it can be restarted. This feature prevents damage to the compressor caused by rapid cycling. However, most do not provide a delay when there are power outages--this is the key point.
    All Honeywell thermostats provide a delay when there is a power failure in the cooling position. Basically the thermostat takes the power loss as a fresh call for cooling with the standard delay as if it was a normal cycle delay. Try it. Cut the power off to the section of the unit that contains the 24 volt supply. Then reenergize the unit and the thermostat will delay the cooling call to the condenser unit. Now power surges are a different story and a time delay does not help there.

    One final note. If you try to hook up a time delay and also use a thermostat with a time delay all you do is extend the delay which will make the house uncomfortable since the total delay will be so long.
    TxGreaseMonkey's Avatar
    TxGreaseMonkey Posts: 16,761, Reputation: 5597
    Uber Member
     
    #7

    Jul 12, 2007, 08:09 AM
    Many Hunter and other less expensive thermostats do not provide delays, when there's a power outage.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #8

    Jul 12, 2007, 08:50 AM
    I never sell cheat stats. They are not worth selling because of all the problems
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #9

    Jul 12, 2007, 06:20 PM
    Quote Originally Posted by acetc
    You may be on the right track BUT I think you ment a time delay relay to delay on make, not break and nix the scerw driver trick, use a volt meter.
    Time delay on make is like a heat sequencer, every time you have a 24 volt call, it times on (every time). Time delay on break means after the 24 volts is broke it will have to be off for that amount of time. Even if it is calling for it to close again.
    hvacservicetech_07's Avatar
    hvacservicetech_07 Posts: 1,083, Reputation: 75
    Ultra Member
     
    #10

    Jul 12, 2007, 08:42 PM
    Quote Originally Posted by txgreasemonkey
    Many Hunter and other less expensive thermostats do not provide delays, when there's a power outage.
    Those thermostats would better serve as paper weights.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Rheem RACB-030JAS residential A/C unit condenser fan motor replaced [ 26 Answers ]

I just replaced the condenser fan motor and it initially spun up then stopped, after 10 minutes it ran again then stopped. Now I can hear it buzz then stop but not spin. The original motor was a GE 5KCP39BG K075CS 1/6 HP 1075 RPM 208/230 V its replacement a Dayton 4M205G 1/4 hp 1075 RPM ...

Outside unit doesn't come on when thermostat turns inside unit on so no heat? [ 1 Answers ]

My thermostat will trip my heater to turn on. The inside blower turns on but the outside unit doesn't turn on. I can get it to go by turnign off the unit at the thermostat and waiting a minute. I turn it on and off until I hear the outside unit turn on. The problem is when the Thermostat turns if...

Timers for Internet [ 1 Answers ]

How do I set up timers for my kiddos when they get on the Internet so that they can only stay on the Internet for a certain amount of time? Thanks- Ann

Replacing A/C - condenser or heat pump/condenser [ 1 Answers ]

I live in a condo. All of the units in the building need to new air conditioners because they are all old and will not survive a scheduled reroofing of the building. The association got a bid for a company that will put in a new condenser unit for anyone who wants one - it is about $1500 installed....

Replacement of electric unit with gas unit in mobile home [ 2 Answers ]

#1 Dec 27, 2006, 10:32 PM vcavina New Member Join Date: Dec 2006 Location: California Posts: 7 Electrical wall heater in single wide mobile home


View more questions Search