Ask Experts Questions for FREE Help !
Ask

Closed loop Chilled water system - pressurisation units

Asked Nov 20, 2006, 10:37 AM — 18 Answers
Hi all ,

I am new to this site...

Could you please some one help me out to locate the the pressurization unit for a chilled water system application in 120m tower building. The heat exchangers/CHW pumps are located at 0.0 level...System volume is about 35-40 m3 and pump head is around 4 bar...

What is the ideal position of pressurization units... And what would be cut in & cut out pressure settings for the unit..I would appreciate if you can give the selections too

I would appreciate the earliest response

Thanks & Regards

18 Answers
dulenz's Avatar
dulenz Posts: 14, Reputation: 10
New Member
 
#11

Nov 4, 2008, 03:11 PM
You can locate pressurisation unit anywhere you want. If your chiller and pumps are located on level 0 than locating the pressurisation unit at highest level will make it smaller and cheaper than if you locate it on level 0. However bare in mind that it might not be feasible to locate pressurisation unit at highest level (no plantrooms).

Cut in and out points will depend on pressure in piping that you want to keep. When pumps are not operating the pressure in piping should be above atmospheric (positive gauge) at all points of the system to prevent air infiltration. Typically you need around 30 kPa positive pressure.

ASHRAE formulas are ok. For sizing

Chilled water is closed system so pumps should be sized for pressure loss through piping, coils and fittings only! Not for static head.

Location of the pressurisation unit has nothing to do with pump selection. Pumps will be the same wherever you put your pressurisation unit.


Let me know if you need more help
Helpful
Gouravnim's Avatar
Gouravnim Posts: 2, Reputation: 1
New Member
 
#12

Jun 9, 2009, 02:46 AM
How to calculate the head and flow for chilled pumps primary & secondary?
Helpful
ronald123's Avatar
ronald123 Posts: 1, Reputation: 10
Junior Member
 
#13

Jan 9, 2012, 03:42 AM
Dear kdagencies,

Appreciate your answer.
What about the flow rate capacity of the pressurization pump?

To anvarpb,
What is the Q in your equation above?
Is it the sensible heat you mean?

Hope to hear you soon.
This is a good thread to share ideas.
Helpful
baneshpai's Avatar
baneshpai Posts: 1, Reputation: 1
New Member
 
#14

Apr 30, 2012, 11:43 AM
I was following above questions. can anybody tell me what will be the pressure at the highest / top level of the building?
Helpful
Chill Man's Avatar
Chill Man Posts: 1, Reputation: 1
New Member
 
#15

Sep 26, 2012, 07:00 AM
I like to add a smole correction for this. If consider the pump head as same as the hight of the building you will never reach to the top. First calculate the head loss of the piping arrangement and add that to this. That is your pump head. But do not forget to keep the safety factor.
Helpful
Alireza Avizheh's Avatar
Alireza Avizheh Posts: 1, Reputation: 1
New Member
 
#16

Nov 25, 2012, 03:13 PM
Hi
And also for calculating open exp. tank volume you can use below eq.

V = 1.5 x ( Q / 1000)
Q = boiler heat Capacity, Kcal/hr
V = open exp. tank volume, Lit.
Helpful
jumayjuma's Avatar
jumayjuma Posts: 1, Reputation: 1
New Member
 
#17

Dec 2, 2012, 05:33 AM
Salam
This is a common problem in New Dubai
Was sudden District Cooling become the favorite choice for newly developed towers because of more investment advantages?
However
Observations:
* Secondary chilled water pumps are at full speed (VFD) and sometimes even stand-by pump is on.
* Lower floors tenant are paying high energy (BTU Meter) Bills.
* Higher floors are not getting enough cooling.
* When humidity level rise, condensation & fungus will hit the tower.
* DC-Provider is not satisfied of less cooling consumption
Reasons:
* Form of air pockets.
* Wrong location of Chilled Water Pump
* Wrong location of make-up pressurization pumps
* Using bad quality of Air Vent Valves
* Unbalanced chilled water system (Can't be balanced as it is)
* DC-Provider control the flow depending on Temp. Diff, while tower control's flow depending on Pressure, no integration or communication between both systems
For Corrective Action & Solution
Please send me your e-mail so I will send you a presentation
Thanx
Eng. Juma Yousef
Getco-Green Earth Technology Co.
+971-50-4948385
jumayjuma@gmail.com
Helpful
Patrik-bc's Avatar
Patrik-bc Posts: 2, Reputation: 1
New Member
 
#18

Apr 25, 2013, 05:38 AM
Dear Caibuadday,

In a chilled water system (primary secondary and tertiary pumps with chillers), how to determine the maximum allowable pressure at the pressurozation unit to use in the calculation it is too much confusing and not clear for chilled water system.

And if the pressurization unit is installed at the suction of the pump how it keeps the pressure constant at this point? In other way if we install the pressure unit at the discharge side of the pump why negative pressure will come at the suction?

I wish your supportive answer since no one is able to answer me and even in the BS and ashrae these 2 points not clear.

Thank You so much!
Helpful
Patrik-bc's Avatar
Patrik-bc Posts: 2, Reputation: 1
New Member
 
#19

Apr 25, 2013, 05:41 AM
Quote:
Originally Posted by dulenz View Post
You can locate pressurisation unit anywhere you want. If your chiller and pumps are located on level 0 than locating the pressurisation unit at highest level will make it smaller and cheaper than if you locate it on level 0. However bare in mind that it might not be feasible to locate pressurisation unit at highest level (no plantrooms).

Cut in and out points will depend on pressure in piping that you want to keep. When pumps are not operating the pressure in piping should be above atmospheric (positive gauge) at all points of the system to prevent air infiltration. Typically you need around 30 kPa positive pressure.

ASHRAE formulas are ok. For sizing

Chilled water is closed system so pumps should be sized for pressure loss through piping, coils and fittings only! Not for static head.

Location of the pressurisation unit has nothing to do with pump selection. Pumps will be the same wherever you put your pressurisation unit.


Let me know if you need more help
Dear Dulenz,

In a chilled water system (primary secondary and tertiary pumps with chillers), how to determine the maximum allowable pressure at the pressurozation unit to use in the calculation it is too much confusing and not clear for chilled water system.

And if the pressurization unit is installed at the suction of the pump how it keeps the pressure constant at this point? In other way if we install the pressure unit at the discharge side of the pump why negative pressure will come at the suction?

I wish your supportive answer since no one is able to answer me and even in the BS and ashrae these 2 points not clear.

Thank You so much!
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Hot water not available on some units in my condo [ 9 Answers ]

Hello: I live in a condo where there are 6 units to a building. I recently had to shut off the water supply to the entire building to replace a hot water tap in the kitchen dishwasher as part of a remodeling project (lots of banging, tearing). Now my neighbors downstairs are saying that they...

Water heating system [ 1 Answers ]

I am building a new home (2800 sf each level main and basement) and will be doing a manifold distribution system with PEX piping. With the length of the house, I was planning on a two water heater system. Both 50 gal electric plumbed in tandem. If this seems feasible, would I just supply the...

Restat loop [ 7 Answers ]

Every time I turn my computer on it will go into a restart loop: on,off,on,off etc. Like a continous restart mechanism. On normal bootup I reach the desktop to be met with error messages telling me my System has recovered from a serious error. I click "DOnt send" and another pops up. After...

How do I increase H2O pressure on well system with a water filtration system? [ 2 Answers ]

Howdy, I would like to know how I can increase my water pressure. My current system uses a well pump with a small pressure tank, and "D" control valve. It then runs through a WATERSOFT filtration tank, RAINSOFT water softner, and on the Hot water side, an AQUASTAR on demand hot water system. I...

Water Pressure from Well System Fluctuates [ 2 Answers ]

The flow of water frequently will fluctuate. It will drop some for a 5 or 10 seconds and then resume the original rate. This occurs over a much shorter interval of time than the typical cycle when the pump comes on at 30 PSI to boost the pressure in the tank back to 50 PSI. Our system is 12...


View more Engineering questions Search