Question
 
 
#1  
Old Oct 20, 2007, 03:55 AM
murad79yameen
New Member
murad79yameen is offline
 
Join Date: Oct 2007
Posts: 1
murad79yameen See this member's comment history on his/her Profile page.
chilled water pumps

how i can select the pump after i get the flow required and the head
i have a closed loop system chillers in ground level and 35 floors height
are 4 bars enough to start the system which is the head that i calaculated??
what is system pressure then??
do i have to add the vertical height also to the total of the pump pressure?
the head doesn't represnt pressure of the system is that true?

Reply With Quote
 
     

Answers
 
 
Old Oct 20, 2007, 12:15 PM   #2  
Full Member
caibuadday is offline
 
Join Date: Mar 2005
Posts: 381
caibuadday See this member's comment history on his/her Profile page.
Quote:
Originally Posted by murad79yameen
how i can select the pump after i get the flow required and the head
i have a closed loop system chillers in ground level and 35 floors height
are 4 bars enough to start the system which is the head that i calaculated??
what is system pressure then??
do i have to add the vertical height also to the total of the pump pressure?
the head doesn't represnt pressure of the system is that true?
4 bar only get you up to 11 floor(max, assumed each fl is 12 ft H), 1 bar= 14.7 psi(g), to pump water up to 1 ft H you needed 0.433 psig. A 35 story building require min 182 psig
At 182 psig wont be enough because that is only for the vertical lift, you also have pressure loss due to friction loss( piping and associated fittings , your coil and chiller)
  Reply With Quote
 
     
 
 
Old Mar 19, 2008, 08:29 PM   #3  
New Member
RavenLord is offline
 
Join Date: Mar 2008
Posts: 3
RavenLord See this member's comment history on his/her Profile page.
ya 7abeebi .
first of all u have a 35 Floor Building , and what u require is a minimum of 11.5 bar , and several not just one . always put one on the stand by mode ,

The pump has to be chosen according to both Horizantal and vertical Pipes , Vertical Pipes are important in ur calculation ,
if u are in the Gulf use grandfos Grundfos | The full range supplier of pumps and pump solutions
  Reply With Quote
 
     


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
chilled water pump for HVAC knadeem123 Engineering 8 Apr 25, 2008 01:50 AM
Chilled water pipe dduds79 Engineering 2 Apr 23, 2008 10:09 AM
Chilled water system Vipin Bhatt Engineering 0 Sep 14, 2007 01:00 AM
chilled water pressurization unit raouf Engineering 0 Mar 20, 2007 09:09 AM
chilled water line filter madhusudan Engineering 0 Dec 22, 2006 11:45 PM