| there are many condition to be met in sizing up your transformer to start up a 50hp 3phase ac motor.
1. the starting kva of your motor. (per NEMA code Letter Designation)
2. the voltage sag during motor starting should satisfy the 10% drop requirement.
3. the selection of starter (FVS- full Votage Satrater, RVS- reduce Voltage Starter)
4. the transformer must be sized to its short circuit capability |