Home > Science > Energy   »   Old Westinghouse Circuit Breaker Data Needed:

Question
 
 
#1  
Old Oct 14, 2009, 05:24 PM
hydroguy
New Member
hydroguy is offline
 
Join Date: Oct 2009
Posts: 2
hydroguy See this member's comment history on his/her Profile page.
Old Westinghouse Circuit Breaker Data Needed:

While conducting an arc flash study, I found the following supply breaker on a panel that is 35-40 years old. Westinghouse type QNBRL2100 (quicklag); it is 100amp, 240vac, 2 pole. I am looking for the AIC rating and whether or not it is thermal magnetic, but can not find it listed in the usual sites that sell used bkrs. Any leads on how to find this information?
Thanks

Reply With Quote
 
     

Answers
 
 
Old Oct 18, 2009, 04:33 PM   #2  
Junior Member
Newton1Law is offline
 
Join Date: Jul 2009
Posts: 30
Newton1Law See this member's comment history on his/her Profile page.
I am not familiar with this particular circuit breaker but you may find it listed on the side of the circuit breaker. You will have to remove it from service most likely. Baring that effort, circuit breakers were usually manufactured to certain minimums of AIC. For instance most of todays circuit breakers come with a minimum rating of 10,000 amps AIC. Over 35 years ago, I believe some of the 5,000 amp AIC units were still being used.

As far as to it operating thermally, magnetically or both, usually at the 100 amp level they worked thermally for overload protection and magnetically for fault protection but like you I was not able to find data on that CB unless it was replaced by the Cutler-Hammer BR series of circuit breaker.

Hope this is of some help.
  Reply With Quote
 
     
 
 
Old Oct 19, 2009, 06:06 AM   #3  
Senior Electrical & Lighting Expert
tkrussell is offline
 
tkrussell's Avatar
 
Join Date: Jan 2005
Posts: 5,824
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
I would use 10 KAIC for this device, as it most likely the rating of the unit. You could go back and look for the label. The arc flash energy for a 100 amp at 240 volts is not that hgh as it stands. NFAP 70E calls for Category 1 at the most for this level.
  Reply With Quote
 
     

Your Answer
Email me when someone replies to my answer
Join Login



Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes
Ask your question or search...



Similar Threads
Theory of vacuum Circuit Breaker & sf6 circuit breaker
(8 replies)
Circuit Breaker trips because two bathrooms and master bedroom on same circuit
(2 replies)
Circuit breaker trip after install of GFCI breaker
(3 replies)
gfci breaker + outlet in same circuit.breaker tripping
(4 replies)
Replacing Circuit Breaker with Higher AMP Breaker
(8 replies)

Thread Tools
Show Printable Version Show Printable Version
Email this Page Email this Page
Search this Thread

Advanced Search

Bookmarks





Copyright ©2003 - 2009, Ask Me Help Desk.
All times are GMT -8. The time now is 06:58 AM.