    Wiring single pole thermostat in double pole fixture
    Hello,

    I am trying to install a line voltage programmable thermostat into a manual thermostat fixture. The programmable thermostat is Honeywell RLV430. Instruction manual here:

    http://www.homedepot.ca/wcsstore/Hom...8044b91564.pdf

    The existing fixture has 2 red wires and 2 black wires, the thermostat has only 2 black wires.

    My question is, which colored wire should pass-through? I think red, however would like to hear some expert opinion.

    Please let me know.

    Thanks!
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 14, 2007, 07:38 AM
    If you are located in the USA, then the National Electric Code applies, and a 1 pole thermostat is not allowed for a 240 volt heater, because both hot legs must be opened when the thermostat is turned off and used as the required disconnecting means.

    If you are in Canada, then I believe a 1 pole thermostat is allowed for 240 volt heaters, but best to check first with local code.

    I would not ask the clerk at Home Depot for advice, unless that person is licensed or certified in the electrical trade.
    vjk23's Avatar
    vjk23 Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 14, 2007, 10:00 AM
    Thanks tkrussel,

    I am in Seattle, WA. I bought this thermostat as this is the only programmable thermostat available for baseboard heaters.

    Can you recommend any other programmable thermostat for controlling electric baseboard heaters?
    dood007's Avatar
    dood007 Posts: 2, Reputation: 1
    New Member
     
    #4

    Feb 23, 2013, 07:26 PM
    This article is still helping people 6 years on!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wiring Hot Tub and using a 50 Amp Double Pole GFCI Circiut Breaker [ 10 Answers ]

:confused: I keep getting the GFCI breaker tripping after wiring my hot tub. I wired 2 hot Red and Black to the proper terminals and the White to the neutral and the Bare Copper to the ground Post at the tub. I am using 6-3 w/G per instructions. Could the GFCI breaker be bad? When I wire...

20 amp double pole gfci [ 9 Answers ]

I am working on an addition and am installing a whirlpool tub. The tub requires 2 - 20 amp GFCI protect circuits: 1 for the pump and 1 for the heater. I ran 12/3 wire in the walls thinking I could have the BLACK wire go from 1 GFCI breaker to the pump outlet and the RED wire go from a 2nd GFCI...

240 20 Amp double pole hookup [ 3 Answers ]

So this site is great, thanks Ok my next question is if I have a 12-2 wire at the baseboard then I would hook-up the dual-pole 20Amp at the box with both the white and black into each of the breakers connection and of course the ground to ground, no nuetral, right? Steve

Installing double pole wall t-stat baseboard heater [ 2 Answers ]

I have a 220 baseboard heater, and it is on dedicated circuit. Heater works okay as I have run wires straight through and turned on circuit breaker and heater works. This is a Marley baseboard heater and wall double pole thermostat. Instructions with thermostat leave a lot to be desired. Actual...

Casablanca Fan with Single pole, triple throw, with off position [ 3 Answers ]

Witch Color goes into which electrical connection: We have black, grey, pink and yellow colors and stations L-1-2-3 Thanks


View more questions Search