| You may see Line and load marked on the thermostat. If you do, line goes to the fuse and load goes to the heater.
Since this is likely a 240 ckt, you need to interrupt both legs.
Power needs to flow thrugh the switch. If the wires to the heater are black and white, then the whites on the switch should interrupt the white and the blacks interrupt the black.
What happens, is the thermostat disconnects both poles in the off position. In the on position, one pole is controling the power to the heater and the other pole is on all the time. |