Question
 
 
#1  
Old Jul 7, 2008, 07:44 AM
wildarking
New Member
wildarking is offline
 
Join Date: Jul 2008
Posts: 1
wildarking See this member's comment history on his/her Profile page.
Wiring 125 Amp Sub Panel

I have a cutler Hammer 125 amp main lug panel that I have installed for a sub panel to feed an out door kitchen and a sun room. The sub panel has 2 lugs for connecting hot wires and 1 lug for connecting a neutral. The sub panel will feed 4 ceiling fans, 9 lights,
1 bath heater, 1 refrigerator and 10 receptacles. The sub panel does not have a ground bus bar. Do I connect the ground wires with the neutrals? Do I run a ground from the 200 amp main breaker panel to the sub panel? If so, where does it connect since there is no ground lug? It is approx. 80 feet from the main breaker panel to the sub panel. What size wire would I need to run? What size breaker do I need to put in the main panel to feed the sub panel?

Reply With Quote
 
     

Answers
 
 
Old Jul 7, 2008, 08:18 AM   #2  
Engineering & Electronics Expert
KeepItSimpleStupid is online now
 
KeepItSimpleStupid's Avatar
 
Join Date: Aug 2007
Posts: 4,596
KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.
The largest breaker you'll be able to get will proably be 100 Amps.
If you were using 100 A, then #1/3 NM-B copper with ground can be used for 80'.

Can't size the panel because you left the loads out. This is a maximum.
You didn't give any loads and voltages of the loads.

You have to buy a ground bar kit for the sub-panel. Grounds and neutrals must be separate in the sub-pane. If the sub is in a detached structure, then a ground rod is needed.

4 wires need to be run back to the main panel. If copper, then 3 #1's and 1 #8.

Grounds and neutrals must be isolated in the sub-panel.
  Reply With Quote
 
     


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
Sub Panel Wiring Milo Dolezal Electrical & Lighting 4 Jun 26, 2008 06:03 AM
Wiring from my house panel to my pole barn panel DBRE1234 Electrical & Lighting 1 May 6, 2008 07:47 PM
Wiring to sub-panel. duckydo Electrical & Lighting 1 Aug 30, 2007 02:36 PM
Sub panel wiring Jerry2Wire Pools - Spas & Saunas 1 Jan 12, 2007 05:51 AM
sub panel 40 amp wiring canyonman Electrical & Lighting 1 Aug 31, 2006 11:01 PM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 04:53 PM.