| You can use 4 wire aluminum URD cable, rated USE for direct burial. you can use a large conduit as a sleeve for extra protection, and under paved areas for easy replacement if needed.
Or you can use PVC Schedule 40 conduit with all the fittings for a continuous raceway system, and pull aluminum wires with XHHW insulation or THHN/THWN copper wire.
Inside you can use 4 wire aluminum SER cable.
For 200 amp residential, you can use 3- #4/0 Al or 3-#2/0 copper. The fourth wire, equipment grounding conductor, can be minimum #6 copper or #4 al.
Be sure to connect the neutral, equipment ground, and the grounding electrode conductor all together at the main disconnect. The neutral and equipment ground will be separated at the panel. |