Ask Experts Questions for FREE Help !
Ask

Wire sizing and conduit sizing

Asked Apr 10, 2007, 01:55 PM — 8 Answers
I am looking for confirmation on some of the info I have found and answers to a few missing pieces. This is regarding wire size and conduit size for service conductors from the meter to the breaker panel (about 30 ft away).

Wire Size:
125A service needs #2 copper or 1/0 aluminum -- #6 copper ground.
150A service needs #1 copper or 2/0 aluminum -- #6 copper ground.
200A service needs 2/0 copper or 4/0 aluminum -- #4 copper ground.

Is this correct? These would each be 3 wire services plus ground. Do all 3 wires have to be the same size or can the neutral be smaller? If so, how much smaller?

Conduit:
How deep does PVC conduit for this run need to be (no driveways involved)?
What diameter PVC conduit is needed for each of the services above?
Specifically I am looking at either 125A or 150A service and would like to use a conduit big enough so that someday in the future I could run another set of wire back through this conduit that would provide photovoltaic current back to an REC meter (and back to the grid). Is 2.5 inch conduit adequate for what I want now and in the future?

THANK YOU!

8 Answers
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#2

Apr 10, 2007, 05:03 PM


Wire Size:
125A service needs #2 copper or 1/0 aluminum -- #6 copper ground.
150A service needs #1 copper or 2/0 aluminum -- #6 copper ground.
200A service needs 2/0 copper or 4/0 aluminum -- #4 copper ground.


All correct.

These would each be 3 wire services plus ground.

Correct.


Do all 3 wires have to be the same size or can the neutral be smaller? If so, how much smaller?

The neutral can be 70 % of the line connected load amps rating.


Conduit:
How deep does PVC conduit for this run need to be (no driveways involved)?

Minimum is 18" deep, a warning tape 6-12 in below grade is not required but a cheap insurance to digging up a feeder later.

What diameter PVC conduit is needed for each of the services above?

No nit picking here, use 2" for all sets, and always use wire lube.

Specifically I am looking at either 125A or 150A service and would like to use a conduit big enough so that someday in the future I could run another set of wire back through this conduit that would provide photovoltaic current back to an REC meter (and back to the grid). Is 2.5 inch conduit adequate for what I want now and in the future?

I would not suggest large cable be pulled in later alongside existing cable. If both sets of cable will be drawing power at the same time, derating is needed, so the next size wire may be needed for some sizes. Sorry but a fair amount of calcs are need each size each wire.

3" is needed for #4/0's.

Sorry but Jennifer Lopez is on Idol, so I got to see this.

I will check back later.
Helpful
ptnoble's Avatar
ptnoble Posts: 42, Reputation: 1
Junior Member
 
#3

May 14, 2007, 09:32 AM
[quote=tkrussell]Wire Size:
125A service needs #2 copper or 1/0 aluminum -- #6 copper ground.
150A service needs #1 copper or 2/0 aluminum -- #6 copper ground.
200A service needs 2/0 copper or 4/0 aluminum -- #4 copper ground.


All correct.

These would each be 3 wire services plus ground.

Correct.


Do all 3 wires have to be the same size or can the neutral be smaller? If so, how much smaller?

The neutral can be 70 % of the line connected load amps rating.

SO, For a 100A service, can I have my two hots be #4 copper and the neutral be #6 copper?

THANKS
Helpful
ptnoble's Avatar
ptnoble Posts: 42, Reputation: 1
Junior Member
 
#4

May 14, 2007, 09:33 AM
SO, For a 100A service, can I have my two hots be #4 copper and the neutral be #6 copper?

THANKS
PTN
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#5

May 14, 2007, 04:06 PM


Only if doing the load calculations to arrive at the maximum unbalanced current and the load is no less than 65 amps for a #6 THHN/THWN wire.

Most likely it will be less, I have no idea of the loads, and I just didn't want to say yes without explaining why.
Helpful
abcsalem's Avatar
abcsalem Posts: 70, Reputation: 9
Junior Member
 
#6

Oct 17, 2007, 08:19 AM
Quote:
Originally Posted by tkrussell
[i]Wire Size:
No nit picking here, use 2" for all sets, and always use wire lube.
Tk, do we need to use wire lube, if one is to use metal conduit?
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#7

Oct 17, 2007, 04:20 PM


The quality of wire lube nowadays, it is worth the cost and effort. The biggest risk to pulling wire is the friction,esp for long runs.
Helpful
Lola71078's Avatar
Lola71078 Posts: 1, Reputation: 1
New Member
 
#8

Apr 30, 2012, 10:32 AM
What size grey conduit do I need to run two 4/0 alluminum wire through?
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#9

May 1, 2012, 03:40 AM
Minimum size of Schedule 40 PVC conduit would be 1-1/2", assuming XHHW insulation on the 2- #4/0 Al.

Depending on length, it may be wise to upsize the conduit.

May I ask why only two conductors?
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Earth wire cable sizing [ 3 Answers ]

Hi , I'm mike, 29 years old, I live in Mauritius. I would like to know how to size my eathing wire since my supply wire is 6 mm2. Thanks

Proper wire sizing? [ 3 Answers ]

We are re-routing the supply line to our pump house, where there is an extension panel with 30A 220V (pump controller) and 15A & 20A 110V breakers. It's about a 60' run from the 200A main service in the house, being placed in conduit 2' underground. The wire in place is newer 10 gauge solid copper....

Wire sizing for sub panel. [ 1 Answers ]

Thank you for the response on my sub panel questions. I finally found a slim line breaker which will work in my main panel. I can now consolidate two breakers to give me room for a 100 ap breaker. This breaker will feed the sub panel in my workshop. I plan on placing a 100 amp sub panel in the...

Electrical sizing help [ 5 Answers ]

I am currently building a new building. We as the owners have decided to install a diesel back-up generator unit with auto transfer. The building uses well water and therefore requires a water storage tank for the fire suppression sprinkler system. It also will be using a 100 hp 480 volt 3 phase...

Conduit sizing? [ 4 Answers ]

Hi all! I am relocating my breaker box approx 30 feet from its original location. Installing splice box in the old location for connections. My question is : I have 14 12-2 and 3 12-3 to pull from new box to splice box what size conduit do I need so not to worry about heat build up or de-rating...


View more Electrical & Lighting questions Search