    dgley's Avatar
    dgley Posts: 4, Reputation: 1
    New Member
     
    #1

    Apr 24, 2010, 05:25 AM
    When running underground wire from one disconnect to another 100 feet away do I need
    I am installing 400 amp service with two 200 amp disconnects and then running direct burial alum wire to another 200 amp disconnect 100 feet away due I need to run a ground wire in that underground wire bundle to connect to the two disconnects as long as I separate 200 amp disconnect ground and the nuetral at the last diconnect
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Apr 24, 2010, 05:35 AM

    You DO need an equipment grounding conductor between the service equipment (main disconnect) and any/all panels.

    There used to be certain conditions which allowed a 3-wire feeder omitting the equipment ground, but this has been removed from the code.
    dgley's Avatar
    dgley Posts: 4, Reputation: 1
    New Member
     
    #3

    Apr 25, 2010, 01:33 AM

    Thanks for your help
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Apr 25, 2010, 04:04 AM
    Isn't that what I stated here:

    https://www.askmehelpdesk.com/electr...ct-466657.html

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What size wire for 220v 100 amp service at 100 feet [ 7 Answers ]

I am running 220v 100 ft to a 125 amp sub panel. A welder would be the heaviest thing used. (around 200 amp welder) what size copper wire would I need running in pvc underground

How many feet of wire between main breaker and meter base without a disconnect [ 1 Answers ]

What is the code for the length of wire between the panel box and meter base without installing a disconnect

Wire size for a 100 amp sub panel 200 feet away [ 8 Answers ]

I have a 200 amp main panel in my house and I just built a garage and am planning on putting a 100 amp sub panel in the garage. The garage is about 200 feet from my house and it has a 2 inch pvc stubbed out underground. I am wondering what size aluminum I would need to feed it, and if I can use a...

Gauge of Wire From Meter to house,100 amp fuses,200 feet run. [ 2 Answers ]

Hello, I am intending to replace some wire that runs for 200 feet, from my meter to my house.I live on an island, so the run is quite long ! At either end are breaker boxes with 100 amp fuses in each.Never had any trouble/ fuse blows etc. The old wire (each of the 3 strands) are a little...

Running THHN wire above 8 feet. [ 3 Answers ]

I am wiring a barn/shop area and have run all wiring in EMT conduit except above 8 feet where I have run some ROMEX to lights. My question is: I need one extra wire for a 3-way switch traveler wire. Can I staple this along side of the ROMEX wire above 8' in the hi bay area, or does it have to be in...


View more questions Search