    MeatyPortion Posts: 2, Reputation: 1
    New Member
     
    #1

    Mar 19, 2012, 05:15 AM
    What size wire will I need for 120' run of 100 amp service?
    I have a 200 amp main. I will need to run 100 amp service to a mobile home that is 120 feet away. I have schedule 40 pvc 24" deep for the run. My panel has been green tagged and my trenching and conduit approved. I paid the local power company $5600.00 to run power to my land 1300 feet away from the closest pole. I thought they were going to run all of the wiring but found out they will only run to my main. My 200 amp main is 120 feet away from the 100amp sub on the mobile.

    I need to know what size wire I will need to run for this. I prefer copper but the cost may change that to aluminum. The house will have a 220 volt dryer and an electric water heater. The AC will have it's own run from the main, other than that just the typical 3 bed home.

    Thanks for your time!

    Thank you for your time
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Mar 19, 2012, 06:18 AM
    What size Sch 40 PVC conduit is installed?

    Assuming a full load of 80 amps allowed on a 100 Amp feeder, 240 volts and 120 feet, I arrive at:

    Copper would need 3 #3 and 1- # 8 for equipment ground,

    Or,

    Aluminum would need 3 #1 and 1- # 6 for equipment ground.

    Insulation types can be either THHN/THWN, or XHHW, or USE.
    MeatyPortion's Avatar
    MeatyPortion Posts: 2, Reputation: 1
    New Member
     
    #3

    Mar 20, 2012, 03:25 AM
    2-1/2" conduit with two 24" sweeps.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Mar 20, 2012, 04:09 AM
    OK, conduit is large enough for the wire I suggested.

    Keep in mind in the future, some local codes and utilities require, for good reason, steel sweeps with PVC conduit.

    Long runs of wire can burn through the PVC sweeps, so go easy with the pull.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Size of wire 100 amp garage service? [ 1 Answers ]

I will actually be using less than 60 amps but the box has 100 amp breakers and rating. Do I need to go to a larger gauge simply because of the larger breakers or can I go smaller as for a 60 amp usage? I have a small compressor; 50 amp welder; may install a motorized garage door as a manual is...

What size wire for 220v 100 amp service at 100 feet [ 7 Answers ]

I am running 220v 100 ft to a 125 amp sub panel. A welder would be the heaviest thing used. (around 200 amp welder) what size copper wire would I need running in pvc underground

Wire UF wire to run to new 100 amp service panel? [ 10 Answers ]

My house has a 200 amp service. I have a new 30x40 building in back. I have a 100amp Square D load center for the building. I want to run a line from the house to power the building. Big items include, air comp 30 amps, welder 50 amps, other raidial arm saw, ban saw pipe saw 15-20 amps? It is...

Can I run a 50 amp subpanel if a 100 amp main if so what size wire [ 1 Answers ]

Can I run a 50 amp subpanel from a 100 amp main and if so what size wire

Trying to run 2 100 amp subpanels -what size wire? [ 3 Answers ]

Ok, I am new to the site, but I have looked and looked and not found the answer to my specific questions. Many questions are similar but do not have the same specific circumstances and I have asked many people including electricians and I get different answers from everyone I ask so I am seeking...


View more questions Search