    What is the maximum size 3 wire copper can go in 3 inch pvc
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Dec 31, 2010, 09:16 AM

    26 in Sch80
    30 in Sch40


    I have to say, this is an extremely odd request. Is it for a test or homework or something?
    Anyone really needing to know this would have a copy of the NEC and would know exactly where to look.

    May I ask why you are asking this?
    linejoc's Avatar
    linejoc Posts: 8, Reputation: 1
    New Member
     
    #3

    Dec 31, 2010, 09:38 AM
    Comment on stanfortyman's post
    We have an under sized generator and have to upgrade it to a 100 kw and the feed from the generator now is 4/0-2/0 AL in 3 in conduit 250 feet from the house
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    Dec 31, 2010, 10:03 AM

    OH!! You asked how large of a 3-wire. Not how many #3 conductors. Sorry.

    You would NOT run a "3-wire" cable in conduit. You would run 3 or 4 individual conductors.

    I have to say, anyone who does this for you will know what to do.

    You really need a 100kW(!? ) genset for a house? For real? Sounds like a real mansion, not even a McMansion.
    linejoc's Avatar
    linejoc Posts: 8, Reputation: 1
    New Member
     
    #5

    Dec 31, 2010, 10:12 AM
    Comment on stanfortyman's post
    Believe me it is the 48kw is to small keeps tripping out we are pulling close to 300 A right now
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #6

    Dec 31, 2010, 10:19 AM

    10,000+ sq/ft?

    What could you POSSIBLY be running that you are tripping a 48kW genset??
    Are you familiar with the idea that you do not have to run everything in your house during emergencies?
    linejoc's Avatar
    linejoc Posts: 8, Reputation: 1
    New Member
     
    #7

    Dec 31, 2010, 10:41 AM
    Comment on stanfortyman's post
    I said it is a mansion all the floors are radient heat etc.
    linejoc's Avatar
    linejoc Posts: 8, Reputation: 1
    New Member
     
    #8

    Dec 31, 2010, 10:49 AM
    Comment on stanfortyman's post
    That is 300A on each leg we are looking to upgrade to a 800A service
    linejoc's Avatar
    linejoc Posts: 8, Reputation: 1
    New Member
     
    #9

    Dec 31, 2010, 10:51 AM
    Comment on stanfortyman's post
    That is for the main house the guest house also runs off the genset it is only a 200A service
    linejoc's Avatar
    linejoc Posts: 8, Reputation: 1
    New Member
     
    #10

    Dec 31, 2010, 11:18 AM
    Comment on stanfortyman's post
    I know I need 3 individual conductors what is the largest copper I can put in 3 in PVC I need to know if I have to upgrade the conduit
    aguywithfeet's Avatar
    aguywithfeet Posts: 29, Reputation: 3
    New Member
     
    #11

    Jan 4, 2011, 04:10 PM
    If the PVC is schedule 40 (thinner stuff) and the wire is THHN which is most common. You can put 3 700 MCM(kCM). You may need a ground too though which will be considered in the pipe fill. This was installed by a licensed electrician right? If so one would hope it was done right. It is overlooked by a lot of home owners though. And good for you for having a gigantic house.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #12

    Jan 4, 2011, 04:14 PM
    Quote Originally Posted by aguywithfeet View Post
    And good for you for having a gigantic house.
    :rolleyes:

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search


Check out some similar questions!

How do join half inch PVC Pipe to 1 1/2 PVC [ 1 Answers ]

I am replacing a 1 1/2" tub drain with a 2" shower drain. The existing 1 1/2 PVC Tub Drain leads into 2 " on the main sewer line. Is three a way to remove the 1 2/2 line (maybe ream out the 1 1/2 pipe thats fitted into the 2 "??

Can you replace a 4 inch cast iron soil stack with 3 inch pvc? [ 3 Answers ]

I recently purchased a home built (I'm guessing) in the early 1900's. I noticed a leak in my basement coming from the old 4 inch cast iron soil stack running from my second floor bathroom to the basement. There is water dripping down the pipe to the basement. Three plumbers have come out to...

How do I connect 3 inch sch 40 to 3 inch copper . The o. D. Of the copper is 3 inch [ 2 Answers ]

I am remodeling an old house with all copper plumbing except for the cast iron that comes out of the basement floor. Some of the copper drain line is bad so I am trying to connect to the copper with sch 40 3 inch pipe. I can't seem to find a no hub band to make the connection. The o.d. of the...

How to connect 1 1/2 inch copper pipe to PVC [ 2 Answers ]

I have a 1 11/2 in diameter copper drain pipe and need to connect it to a PVC pipe. What's the best way to do this? Thanks

Size of Copper/pvc inside new home to max pressure from 3,000 gl tank on hill [ 1 Answers ]

Hi, I am building a new home in the country and have a 3000 gallon water tank 75 verticle above my (future) second story. I was going to have either 2" sch 40 pvc or 1 1/4" come down the 160 feet to my home. And then I wanted to know what is the largest copper pipe I could use inside the home to...


View more questions Search