Question
 
 
#1  
Old Nov 7, 2009, 03:52 AM
Scleros
Hardware Expert
Scleros is offline
 
Join Date: Feb 2007
Location: Virginia USA
Posts: 1,589
Scleros See this member's comment history on his/her Profile page.Scleros See this member's comment history on his/her Profile page.
Welder wiring

I need to wire for a MIG welder (Miller 211). Manual recommends max. 25 A circuit breaker with trip curve comparable to time delay fuse and min. 14 gauge wire per NEC Table 310.16. I'm thinking I would like at least one but perhaps two 120V 20A outlets for light, grinder, etc. Initially, I thought I could run 14/4 and put an outlet on each leg, but then got to thinking what would happen in the event one of the 120V devices faulted but not enough to trip the breaker. This setup would also asymmetrically load the two legs when using both the welder and a tool, although that isn't very likely and could trip the breaker.

So, the questions that come to mind:
1. What is correct way to wire this?
2. 14 gauge seems light?

Reply With Quote
 
     

Answers
 
 
Old Nov 7, 2009, 04:20 AM   #2  
Senior Electrical & Lighting Expert
tkrussell is offline
 
tkrussell's Avatar
 
Join Date: Jan 2005
Posts: 5,816
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
I am not seeing what you mention for specs in the datasheet:

http://www.millerwelds.com/pdf/spec_sheets/DC12-54.pdf

If your manual states #14 wire, then go for it, but I would run #12.

If you run 4 wire cable, that would be two circuits, each with a separate neutral?

You do mention "run 14/4 and put an outlet on each leg", so you plan on using a shared neutral?

I would not recommend that either.

Circuits using shared neutral should be protected ith the same size rating circuit breaker.

Has this helped? If not can you elaborate?
  Reply With Quote
 
     
 
 
Old Nov 7, 2009, 04:42 AM   #3  
Hardware Expert
Scleros is offline
 
Join Date: Feb 2007
Location: Virginia USA
Posts: 1,589
Scleros See this member's comment history on his/her Profile page.Scleros See this member's comment history on his/her Profile page.
Quote:
Originally Posted by tkrussell View Post
I am not seeing what you mention for specs in the datasheet:
The wiring info is in the manual on page 18.

Quote:
Originally Posted by tkrussell View Post
If not can you elaborate?
I was thinking out loud if two 120V outlets could be pulled off a single 240V circuit and have everything work properly in the event of a fault, and what I was thinking seemed to run into a logical dead end for having the 120Vs protected properly. So, is running a 240V circuit and two separate 120V circuits each with appropriately sized breakers the proper way to do this? If so, is there a single armored cable for doing it in one run or is conduit with individual conductors the way to go?
  Reply With Quote
 
     
 
 
Old Nov 7, 2009, 04:50 AM   #4  
Senior Electrical & Lighting Expert
tkrussell is offline
 
tkrussell's Avatar
 
Join Date: Jan 2005
Posts: 5,816
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
OK now I see your unit is 240 volts. The unit will need a separate dedicated circuit.

Since the unit needs a 25 amp breaker, you cannot use the circuit or breaker for 20 amp devices.

There is 4 wire romex or even MC cable available, MC cable has 6 and 8 wire cable available.

Of course, conduit will allow multiple circuits, but cable is available as I mention.

I would be running #12 wire for the welder, and two wires, hot and neutral for each 120 volt circuit.
  Reply With Quote
 
     
 
 
Old Nov 7, 2009, 07:12 AM   #5  
Hardware Expert
Scleros is offline
 
Join Date: Feb 2007
Location: Virginia USA
Posts: 1,589
Scleros See this member's comment history on his/her Profile page.Scleros See this member's comment history on his/her Profile page.
Quote:
Originally Posted by tkrussell View Post
I would be running #12 wire for the welder, and two wires, hot and neutral for each 120 volt circuit.
Then that's what I'll be running unless the inspector has his own ideas. Thanks.
  Reply With Quote
 
     
 
 
Old Nov 7, 2009, 07:40 AM   #6  
Engineering & Electronics Expert
KeepItSimpleStupid is offline
 
KeepItSimpleStupid's Avatar
 
Join Date: Aug 2007
Posts: 9,334
KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.
Is this a garage location or would the installation benefit by installing, say a 60 A sub-panel?
  Reply With Quote
 
     
 
 
Old Nov 7, 2009, 10:56 PM   #7  
Hardware Expert
Scleros is offline
 
Join Date: Feb 2007
Location: Virginia USA
Posts: 1,589
Scleros See this member's comment history on his/her Profile page.Scleros See this member's comment history on his/her Profile page.
I haven't decided where it's going yet. Eventually it will be in a separate workshop fed with it's own service so this is "temporary". I may run exterior outlets and drag everything outside.
  Reply With Quote
 
     

Your Answer
Email me when someone replies to my answer
Join Login





Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

 
Similar Sponsors


Thread Tools
Show Printable Version Show Printable Version
Email this Page Email this Page

Similar Threads
Welder wiring
(1 replies)
Welder wiring
(0 replies)
wiring my new welder
(22 replies)
wiring my new welder
(2 replies)
220 wiring for an arc welder
(6 replies)

Search this Thread

Advanced Search

Bookmarks

Sponsors



Copyright ©2003 - 2009, Ask Me Help Desk.
All times are GMT -8. The time now is 04:27 PM.