    Voltage drop at one outlet
    I have an interesting problem that has me perplexed. My microwave is on a circuit by itself. It quit working. I checked the outlet. It has 88 volts across neutal and hot. I took the microwave down. There is a large plate on the wall that is bolted to the studs. I measure 37 volts between this plate and the neutral of the outlet. I also measure 38 volts between the plate and the neutral of another outlet this is on a different circuit. I took off the plate, put it on the floor and still measured 38 volts. My reasoning was that perhaps one of the screws caught a wire and caused a minor break in the wire thus causing a low voltage, but I would think that there would be just NO voltage if there were a break in the wire. I am confused as to what the problem is. I have checked the CB panel and the breaker is correctly installed and the screw attaching the wire is tight. I have taken off the outlet and measured 88 volts directly between the white and black wire. So, where do you think my voltage is going? This house is only 5 years old! AND it is the only circuit in the house that is being affected.

    Thanks for your help.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jul 27, 2009, 06:45 PM
    Sure sounds like a screw. It can be doing something weird, breaking the wiire and causing a heated connection buried someplace.

    Keep the circuit off until this gets resolved.

    I may be all wet, but better to err on side of caution.

    If you can gain access to the cable before it enter the vertical wall, in basement or attic. I would cut the cable there, with power off, and measure the volts, after turning back on with wires safe at exposed ends.

    If all is good there, I would just run a new cable up the wall to replace the damaged and junction to the good end above or below.

    Could be a bad slice in a junction box. Could be a 2 wire cable from a nearby outlet box where a 3 wire feeder splits, and be a bad splice there.

    These are just examples of real world situations.
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #3

    Jul 27, 2009, 06:58 PM
    Did you check the voltage between the hot and the ground?

    Did you check the connection of the neutral at the breaker panel?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    Jul 27, 2009, 07:04 PM

    There are a couple of key points here:

    1. Circuit all it's own
    2. You checked at the wire at the outlet.

    Let's assume that this is true for the time being.

    Did you check the voltages at the breaker panel?
    At the terminals or at the wire?
    Did you check for loose wires at the breaker?

    There are two other voltages and they are neutral to ground and hot to ground at both locations.

    Voltage is a funny thing when you try to measure it with sensitive meters. Sometimes the results can be misleading.

    One would hope it's a single circuit, but if it were not, then a spice at another outlet could be causing the issues.

    The ground integrity, neutral integrity and hot integrity need to be looked at.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Voltage drop [ 4 Answers ]

Can someone please post the formula for voltage drop? Many thanks.

Voltage drop [ 5 Answers ]

I will be running wire to my shop that is aprox 250' from the main elect box at the house. I would like to have 220 volts and 110 volts. The wire will be buried underground the average temp in my area in the summer is 100 degrees. What size wire should I use. I will be welding with a welder that...

Voltage Drop [ 3 Answers ]

I am trying to illuminate a tunnel about 3000' long temporarily with 9- 400 Watt Metal Halide fixtures spaced about 320' apart. I have a 120/240 generator single phase that I will use to back feed a 240/480 volt transformer to deliver 480 volts, single phase to the tunnel lights. At 480 volts I...

Voltage drop [ 1 Answers ]

The Voltage will drop after 150 meter wire ,how to sole the problem . Thanks to all

Voltage drop [ 2 Answers ]

How far can you run an electrical cord, that is plugged into a 20 amp circuit, and still run a circular saw? If the saw starts slowly, will that harm the saw?


View more questions Search