    Vent fan tripping GFCI receptacle upstream
    I am adding an exhaust fan to my bathroom and wiring it into an existing receptacle which is at the end of a circuit (only one cable in). I took out the old receptacle and metal box, replaced it with a double size blue plastic box(with no ground terminal) and a GFCI receptacle, and wired a single pole switch, inside the new box, between the GFCI receptacle and the fan, thus protecting the fan as required when installed over a tub. I wired according to the diagram I got from a home wiring book:

    BW(Black Wire)from power to GFCI line black, GFCI load black to switch upper terminal, and switch lower terminal to BW of fan.

    WW from power wire nutted with WW from GFCI line white and WW from fan.

    GW from power wire nutted with GW from GFCI ground, GW from fan, and GW which was connected to the original metal box (but led to some place out side up into the wall)*note that no GW is connected to the switch, as my wiring book does not show one*

    When I apply power to the circuit via the breaker box, the GFCI receptacle provides power to anything plugged in, and tests appropriately via the test button. However, whenever I turn the switch to the fan on, I throw the breaker in the GFCI receptacle. When I use a circuit tester (one of those 3-light plug instruments) in the GFCI receptacle as wired above, and push the test button on the circuit tester, this too throws the breaker in the GFCI receptacle.

    Am I being dense for not grounding the switch, as it has a grounding terminal, or am I looking a bigger problem, maybe that the ground wire leading up into the wall really doesn't have a proper ground connection:confused:

    Thanks to the person who grins to themselves, shakes their head, and points out the error of my ways.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 1, 2007, 05:53 AM
    Quote Originally Posted by phdhub1
    WW from power wire nutted with WW from GFCI line white and WW from fan.
    This is what is connected wrong.

    You need to separate these whites so that the LINE white needs to connect to the LINE on the GFI, and the LOAD white must connect to the LOAD on the GFI.

    The ground wire should have a pigtail to the green on the switch, but not having it is not causing your tripping problem.
    phdhub1's Avatar
    phdhub1 Posts: 5, Reputation: 1
    New Member
     
    #3

    Dec 1, 2007, 08:54 AM
    Thanks for the quick response! Let me see if I understand you before I go and try this. I believe you are saying that the white wire from the incoming power should go to the line of the GFCI, and the load white on the GFCI should be connected to the white wire from the fan. Is this right?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Dec 1, 2007, 09:10 AM
    That is correct. The line and load neutrals need to be separated, as being connected is causing the GFI to trip.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Gfci receptacle [ 3 Answers ]

I Would Like To Know If You Can Install A Gfci Recep. On A Shared Neutral Circuit.

Toilet vent upstream? [ 1 Answers ]

Hello, We are putting a half-bath in a small guest house, and I'm having a hard time figuring out if the toilet can be vented with a wet vent (through the sink drain/vent) if the sink is upstream of the toilet. Can anyone tell me? I'm pretty sure (I wouldn't mind some professional confirmation...

GFCI Breaker vs Receptacle [ 1 Answers ]

I'm adding some 20A circuits in my garage/shop and know that they have to be GFCI protected. My question is this: Is there an advantage to using a GFCI breaker over just putting a GFCI receptacle in the first slot of the series? Thanks.

GFCI Receptacle [ 1 Answers ]

Do they make a slimline GFCI Receptacle? I have some very narrow metal eletrical boxes in my kitchen and the regular size GFI will not fit.

Installing a gfci receptacle [ 3 Answers ]

I am trying to install a gfci receptacle in my offfice( replacing the existing regular receptacle) I have two black wires that were wrapped together , two gray wrapped together, one single blue and one green. I followed the directions and think I got all the wires to the right place. The test light...


View more questions Search