    Using 100 amp panel on 200 amp service
    I am building new camp at a site that already has 200 amp service. My power requirements are small and 100 amp will be more than sufficient. Is there any reason I cannot hookup a 100 amp panel to the 200 amp meter socket? Not sure is code allows this. I want to use a small 100 amp panel vs the larger 200 amp.

    Thanks
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #2

    Apr 20, 2007, 01:31 PM
    Why go through the expense of installing a smaller panel when what you have is already more than you need? You will not save money or electricity. Did I miss something?
    Okeyt's Avatar
    Okeyt Posts: 3, Reputation: 1
    New Member
     
    #3

    Apr 20, 2007, 02:53 PM
    Quote Originally Posted by ballengerb1
    Why go through the expense of installing a smaller panel when what you have is already more than you need? You will not save money or electricity. Did I miss something?

    There is no existing panel, only power drop with 200 amp meter socket. I need to install panel and tie into the meter socket. Camp is only 12x20 in size and wanted to keep panel physical size to minimum.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Apr 20, 2007, 03:07 PM
    You could run into problems with the wire sizes. The 100 amp breaker might not take the larger wire. As far as code goes, I wouldn't take the word of anybody here but tkrussel.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Apr 21, 2007, 03:17 AM
    Sure, as long as at the meter, or at the panel, there is a 100 amp main breaker. This will limit the load placed on the meter to 100 amps. The 20 amp capacity feeding the meter will be irrelevant.
    Okeyt's Avatar
    Okeyt Posts: 3, Reputation: 1
    New Member
     
    #6

    Apr 21, 2007, 04:33 AM
    Quote Originally Posted by tkrussell
    Sure, as long as at the meter, or at the panel, there is a 100 amp main breaker. This will limit the load placed on the meter to 100 amps. The 20 amp capacity feeding the meter will be irrelevant.
    Sounds like I have my answer. Thanks for all the quick responses.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Running two 100 amp main panels from a 200 amp service [ 27 Answers ]

Greetings! I live in a rural country area. The electric company will be installing a pole, meter, and 200amp service with disconnect at pole. (It will require 50 foot run of service cable from pole to main load center in mobile). Currently the double wide has a General Electric 100amp Main...

200 amp panel feeding a 100 amp panel roughly 130' away [ 7 Answers ]

Hi all, We are building a apartment above the garage,my question is what size wire do I need to run from the 200 amp panel to the 100 amp panel roughly 130' away? I want to use aluminum wire as I think copper would be to costly. Thanks for your help in advance, Dude :eek:

Running 100 amp service panal 200 ft away from main 200 amp service [ 4 Answers ]

I am looking to find out how big the wire needs to be to carry the load. This will be a 100 amp service coming from a 200 amp main . It will need to travel 200 to 250 ft underground to a barn. If some one could help me that would be great thaxs)))

200 Amp Service Panel with 60 Amp Main Breakers [ 26 Answers ]

I was told when we purchased our house that it had 200 Amp service which it appears to be; however, the top of each bus bars only has 60 Amp breakers for the Main shut offs. Is this normal? Each bus bar is connected to a hot wire (one red and one black) and then the two 60 amp breakers are...

100 amp service vs. 200 amp service [ 5 Answers ]

The house I just bought was built in 1952. It's a 3 bedroom, 1 bathroom with the standard screw in fuses (total amps unknown). Presently I'm doing a remodel. Adding a third bedroom & extra bathroom, washer & dryer, dishwasher, newer & larger refrigerator, bigger microwwave, probably 3 window air...


View more questions Search