Ask Experts Questions for FREE Help!
  Advanced
Register  |  Log in  
   Ask    
 Answer  
  Help  

Ask QuestionsprogressAnswer QuestionsprogressBuild ReputationprogressBecome an Expert
 
Free Answers in 3 Easy Steps

Register Now
3 Steps

At Ask Me Help Desk you can ask questions in any topic and have them answered for free by our experts. To ask questions or participate in answering them you must register for a free account. By registering you will be able to:
  • Get free answers from experts in any of our 300+ topics.
  • Accept money for answers that you provide.
  • Communicate privately with other members (PM).
  • See fewer ads.

Home > Home & Garden > Electrical & Lighting   »   Older 220 volt wire

 
Thread Tools Display Modes
Question
 
 
#1  
Old Mar 29, 2006, 03:37 PM
tstevens83
New Member
tstevens83 is offline
 
Join Date: Mar 2006
Posts: 6
tstevens83 See this member's comment history on his/her Profile page.
Older 220 volt wire

I have an older 220v wire with only 3 wires... 2 hot and 1 ground/neutral (bare). I need to connect (splice) it to a newer 220v wire with 4 wires... 2 hot, 1 neutral (white), and a ground (bare).

And older I mean less than 15 years old.

Reply With Quote
 
     

Answers
 
 
Old Mar 29, 2006, 03:54 PM   #2  
Electrical & Lighting Expert
tkrussell is offline
 
Join Date: Jan 2005
Posts: 4,561
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
So what kind of cables do you have? Probably the old one is BX, withthe metal outer sheathing. If this is the case, the metal sheathing is the "fourth" wire, serving as the equipment ground. The new cable is probably Romex, with the bare equipment ground.

You must use a metal junction box, you need to use an approved connector for the BX cable, and wrench tight the locknut onto the box. The bare wire from the other cable can be connected to the metal box using a machine screw into a threaded hole you will find in the back of the box. This is an approved method to connect the two equipment grounds from each cable together.

Do not forget to install a box cover once you are done splicing.
  Reply With Quote
 
     
 
 
Old Mar 29, 2006, 10:31 PM   #3  
Full Member
PalmMP3 is offline
 
PalmMP3's Avatar
 
Join Date: Jan 2006
Location: New York City (although currently overseas)
Posts: 322
PalmMP3 See this member's comment history on his/her Profile page.
Call PalmMP3 via Skype™ Send a message via MSN to PalmMP3
TK,

Are you sire he isn't referring to an appliance cord (e.g. a three-wire dryer cable that he is trying to tie into a four-wire line)?

Either way, it doesn't sound to me like his "older" cable is BX - he says "I have an older 220v wire with only 3 wires... 2 hot and 1 ground/neutral (bare)" - so he's obviously seeing a bare wire somewhere, not BX armor...

Cheers,
Moishe
  Reply With Quote
 
     
 
 
Old Mar 30, 2006, 01:46 AM   #4  
Electrical & Lighting Expert
tkrussell is offline
 
Join Date: Jan 2005
Posts: 4,561
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
I see your point, I did not pick up that the cable being refered to is SEU cable, two insulated hot wires, with the bare wrapped around the outside of the hots.

Got in late after a long day of electrical work. Sometimes the brain does bnot jive with the eyes.

In this case the 3 wire cable should be replaced with 4 wire, to extend the equipment ground back to the panel. This is probably for a dryer or a range, which now require 4 wire, and there is no other alternative to connecting the ground.

Good catch.
  Reply With Quote
 
     
 
 
Old Apr 2, 2006, 07:11 PM   #5  
New Member
tstevens83 is offline
 
Join Date: Mar 2006
Posts: 6
tstevens83 See this member's comment history on his/her Profile page.
Thanks for the info... I did replace the old wire with a new 4-wire... 75ft of wire. Boy that wire has a mind of its own.

It was for a range. I'm now looking at moving a dryer... hope I don't find the same situation.
  Reply With Quote
 
     
 
 
Old Mar 27, 2008, 09:42 PM   #6  
New Member
Bob V is offline
 
Join Date: Mar 2008
Posts: 4
Bob V See this member's comment history on his/her Profile page.
I am also facing this dillemna - connecting an old 3-wire 220, extending it with a 4-wire. The solution given me by an experience electrician is simply to ground the new green wire to a copper plumbing pipe near the junction box and run the new 4 wire 220 cable back to the panel.
  Reply With Quote
 
     
 
 
Old Mar 28, 2008, 03:09 AM   #7  
Electrical & Lighting Expert
stanfortyman is offline
 
Join Date: Feb 2008
Posts: 1,171
stanfortyman See this member's comment history on his/her Profile page.
Well, Bob, your "experience electrician" is a hack. It has been MANY years since it was legal (or safe) to ground to a local water pipe. They realize how dangerous this could be and dropped that allowance. This is especially true with the boom of Pex and cpvc piping being used.

I am confused, you say you are extending the old three wire cable, yet you say you will run the four wire cable back to the panel.
WHAT exactly are you doing?

I can say with certainty. You CANNOT extend an old 3-wire range circuit. Period.
You MUST run a new 4-wire circuit back to the panel.
  Reply With Quote
 
     
 
 
Old Mar 28, 2008, 05:08 AM   #8  
New Member
Bob V is offline
 
Join Date: Mar 2008
Posts: 4
Bob V See this member's comment history on his/her Profile page.
Stan, thanks for your reply. The situation is an old home built probably in the late 40's or 50s. The kitchen is being remodeled, all the sheetrock removed making it possible to strip out all of the asbestos insulated wire, replacing it with Romex. None of the original circuits will be used. They will be disconnected and capped at the panel. This is where the old 3-wire 220 comes in. It serviced the original electric range but now a gas range will be installed. The breaker panel is an old pushbutton type and unfortunately located at the far end of the home in the basement where it would be impossible to run a new 4-wire cable without a lot of tearout. Plan is to junction that old 220 with a 4-wire cable and run it to a new subpanel in the kitchen which would service new circuits throughout the kitchen. The new 4-wire cable would be grounded to a copper pipe. The original breaker panel is grounded to the pipe where it comes into the house, rather than spikes driven into the dirt, as seems to be the practice now. The electrician in question has 50 years experience, has taught IBEW courses, has owned his company since the 50s and is up on the '08 codes. He knows this isn't exactly legal but doable in light of the situation and budget.
  Reply With Quote
 
     
 
 
Old Mar 28, 2008, 01:16 PM   #9  
Electrical & Lighting Expert
stanfortyman is offline
 
Join Date: Feb 2008
Posts: 1,171
stanfortyman See this member's comment history on his/her Profile page.
Quote:
Originally Posted by Bob V
Plan is to junction that old 220 with a 4-wire cable and run it to a new subpanel in the kitchen which would service new circuits throughout the kitchen.
Knowing what type of cable they used back then it is HIGHLY likely this would not be a legal or safe thing to do. You DO need a 4-wire feeder to a sub-panel.



Quote:
Originally Posted by Bob V
The new 4-wire cable would be grounded to a copper pipe.
NO, it should not! From a legal and safety standpoint.
As I said, this was legal back in 1975, but they soon realized how dangerous this could be.
The piping in a house SHOULD NOT be used as an equipment grounding conductor.
The ONLY time this is safe is IF: a) the water pipe in question is being used as a grounding electrode, and b) you connect your ground within 5' of where the pipe enters the house.
Tell you electrician friend to look up 215.6 Feeder Conductor Grounding Means, 250.134 and 250.130(C).



Quote:
Originally Posted by Bob V
The original breaker panel is grounded to the pipe where it comes into the house, rather than spikes driven into the dirt, as seems to be the practice now.
The practice of using a metallic water pipe as the primary electrode has been around for many years. Newer codes require a supplemental electrode (or two) be installed as well.



Quote:
Originally Posted by Bob V
The electrician in question has 50 years experience, has taught IBEW courses, has owned his company since the 50s and is up on the '08 codes. He knows this isn't exactly legal but doable in light of the situation and budget.
Sometimes some of the old timers make the worst mistakes.
"Doable"??? Budget??? I hate being so harsh, but if your guy would do this he truly is a fool and doesn't value his reputation or your lives very much.

Please have him read those sections I mentioned to show how this is not so "doable".
  Reply With Quote
 
     
 
 
Old Mar 28, 2008, 02:20 PM   #10  
Printers & Electronics Expert
donf is offline
 
donf's Avatar
 
Join Date: Aug 2007
Location: Tidewater, Virginia
Posts: 1,985
donf See this member's comment history on his/her Profile page.donf See this member's comment history on his/her Profile page.
HI guys,

T Steven's did you bother to check for the amperage needed by the new equipment? Were the amperage levels the same?
  Reply With Quote
 
     


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
3-wire home, 3-wire fan, 2-wire remote stolidawg Electrical & Lighting 9 Aug 30, 2006 07:47 AM
Replacing a 240 volt outlet with a 120 volt oulet gstevens97 Electrical & Lighting 1 May 15, 2006 10:28 AM
4 wire home service entrance wire size achovanetz Electrical & Lighting 1 Jan 30, 2006 12:07 PM
2 Wire White-Rogers with no wallplate wire question G_Man Heating & Air Conditioning 2 Dec 26, 2005 05:58 PM
110 volt versus 220 volt mini heat pump rkfowler Heating & Air Conditioning 1 May 21, 2005 04:01 PM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 12:39 AM.