SPA disconnect switch grounding wire requirement

Asked Aug 5, 2007, 02:55 PM — 1 Answer
I'm installing a 240V/60A SPA approximately 85 feet from the house service panel. I'm going to run 3 individual #6 conductors (THN or better) from the service panel to the SPA GFI disconnect box via 1 inch PVC conduit. The SPA is about 7 feet from the disconnect box. The disconnect box instructions suggest that a separate grounding wire from the service panel to the disconnect box is not necessary.---TRUE?
If not true, will a single #10 insulated conductor suffice ar does it have to be the same gauge as the #6 powered conductors? Does the insulation have to be green?

1 Answer
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#2

Aug 6, 2007, 02:36 AM


A #10 green wire is needed as an equipment ground from the panel to the spa pulled in the conduit with the feeder conductors.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Electrical wire size for spa [ 12 Answers ]

Hello, I am wiring up my spa and looking at what info I have (GE / Cutler Hammer) they say for a spa (240) use a 50amp breaker (which I have) and use 8/3 size wire. But looking at my spa where you hook the power up it says use 6 AWG minumin? So which should I use from the house to the breaker...

A/C Disconnect switch [ 7 Answers ]

I am having a 36,000 btu split system installed. This unit is 230/208v with 30 amp breaker. Instead of using the pull out style or lever style disconnects, would it be safe to use a 30 amp 120/277v a/c double pole toggle switch mounted in a appropriate weather proof box as my disconnect?

Ground Wire on Spa Controller [ 1 Answers ]

I just changed the air pressure switch on my SpaBuilders controller for my spa. I noticed that the bare ground wire attached to the left side of the controller was not attached at the other end. I searched, but could not find a likely place to connect this. Where shall I connect this ground...

#12 ground wire for a spa? [ 1 Answers ]

I purchased a used spa from a friend. I am ready to run my electrical connections but I noticed the pig-tail that is on the spa has three 6 or 8 Gage wires for hot and common but the wire that I assume is the ground is only 12 Gage or so. Is this because the ground wire serves only to trip the...


View more Electrical & Lighting questions Search