| If #2 copper is 250 feet long, with a reasonable load of 50 amps, the voltage drop will be 4.9 volts, or 4.8%.
Maximum reccommended voltage drop for a feeder is 3% to the distribution point, or the breaker panel.
#2/0 will offer 2.5 volt drop (2.1%) for the same load. An 80 amp load will result in a 3.25% Vd.
This is acceptable if the branch circuit wiring is not too long, as the final Vd at the outlet should not be more than 5%.
If this was my job I would be selling you #2/0 Aluminum in PVC conduit (if PVC is allowed in your area) The Vd is still a bit high for 80 amps, but here is where what are the chances of a full load being applied. For a 50 amp load the Vd is perfect,2%.
What does the local electrical inspector say about this? |